Troubleshooting Problems in Modules
Section 9-3
9-2-13 Environmental Conditions Check
Note
Prevent exposure to corrosive gases, flammable gases, dust, dirt, salts, metal
dust, direct sunlight, water, oils, and chemicals.
9-3
Troubleshooting Problems in Modules
Coordinator Module Errors
Environmental Conditions Check
No
Is the ambient 
temperature below 
55
°C?
Is the ambient 
temperature above 
0
°C?
Is the ambient 
humidity between 10% 
and 90%?
Is noise being 
controlled?
Yes
Install surge suppressor or 
other noise-suppressing 
equipment at noise sources.
Consider using an air 
conditioner.
Consider using a heater.
Consider using a fan or air 
conditioner.
No
Yes
No
Yes
No
Yes
Is atmosphere 
acceptable?
Consider installing in a panel 
or improving the installation 
location.
No (See note.)
Yes
End
Error condition
Probable cause
Remedy
The Power Supply Unit’s POWER indicator is not lit.
PCB short-circuited or dam-
aged.
Replace the Power Supply Unit.
The RDY indicators on the Modules do not go ON.
The power supply line is faulty
Replace the Power Supply Unit.
The Coordinator Module’s RUN indicator does not go 
ON.
An error in program is causing a 
fatal error
Correct program
The Power Supply Unit’s RUN output* does not turn 
ON.
The Coordinator Module’s RUN indicator is lit.
(*CJ1W-PA205R Power Supply Unit only)
Internal circuitry of Power Sup-
ply Unit is faulty.
Replace the Power Supply Unit.
Motion Control Module does not operate or does not 
operate properly.
The I/O bus is faulty.
Replace the Motion Control 
Module.
A particular I/O point does not operate.
Error occurs in 8-point or 16-point units.
A particular I/O point stays ON.
None of a particular Module’s I/O points will go ON.