Omron FQM1-MMP21 用户手册

下载
页码 414
349
Appendix D
Auxiliary Area Allocations
Auxiliary Area Allocations in Order of Address
The following table lists the Auxiliary Area allocations in order of address. Refer tAuxiliary Area Allocations by
Function
 on page 329 
for a list of allocations by function. 
Read-only Words: A000 to A447, Read/Write Words: A448 to A649
Address
Bits
Name
Function
A000 to 
A015
00 to 15 Subroutine Input Condition Flags
These flags contain the status of the input condition for JSB(982) 
when JSB(982) is used to call a subroutine. 
A100 to 
A199
00 to 15 Error Log Area
When an error has occurred, the error code and error contents 
are stored in the Error Log Area.
A200
11
First Cycle Flag
ON for one cycle after FQM1 operation begins.
12
Step Flag
ON for one cycle when step execution is started with STEP(008). 
A202
00
Motion Control Module slot 1
ON if the Motion Control Module is in slot 1.
01
Motion Control Module slot 2
ON if the Motion Control Module is in slot 2.
02
Motion Control Module slot 3
ON if the Motion Control Module is in slot 3.
03
Motion Control Module slot 4
ON if the Motion Control Module is in slot 4.
A206 to 
A207
00 to 15 Maximum Cycle Time
These words store the maximum cycle time every cycle. The 
cycle time is recorded in 8-digit hexadecimal (unit: 0.01 ms).
A208 to 
A209
00 to 15 Present Cycle Time
These words stores the present cycle time every cycle in 8-digit 
hexadecimal (unit: 0.01 ms).
A400
00 to 15 Error code
When a non-fatal error (user-defined FAL(006) or system error) or 
a fatal error (user-defined FALS(007) or system error) occurs, the 
hexadecimal error code is written to this word.
A401
06
FALS Error Flag
(fatal error)
Turns ON when a non-fatal error is generated by the FALS(006) 
instruction. The FQM1 will stop operating.
08
Cycle Time Too Long Flag (fatal error)
Turns ON if the cycle time exceeds the maximum cycle time set in 
the System Setup (the Watch Cycle Time).
09
Program Error Flag
(fatal error)
ON when program contents are incorrect. 
Module operation will stop.
10
I/O Setting Error Flag
Turns ON when more than four Motion Control Modules are con-
nected to the Coordinator Module. 
14
I/O Bus Error Flag
Turns ON when an error occurs in transferring data between the 
Coordinator Module and Motion Control Modules. Module opera-
tion will stop. 
15
Memory Error Flag (fatal error)
Turns ON when there is an error in the memory. FQM1 operation 
will stop and the ERR indicators on the front of the Modules will 
light. 
A402
05
Motion Control Module Monitoring Error Flag 
(Coordinator Module only)
Turns ON in the Coordinator Module when a system error, such 
as a WDT error, occurs in any of the Motion Control Modules. 
10
System Setup Error Flag
Turns ON when there is a setting error in the System Setup. 
13
Coordinator Module WDT Error Flag (Motion 
Control Modules only)
Turns ON in the Motion Control Modules when a WDT error 
occurs in the Coordinator Module. 
14
Coordinator Module Fatal Error Flag (Motion 
Control Modules only)
Turns ON in the Motion Control Modules when a fatal error occurs 
in the Coordinator Module. 
15
FAL Error Flag
(non-fatal error)
Turns ON when a non-fatal error is generated by executing 
FAL(006). The FQM1 will continue operating.
Address
Corresponding 
subroutines
Word
Bits
A000
00 to 15
SBN000 to SBN015
A001
00 to 15
SBN016 to SBN031
A002
00 to 15
SBN032 to SBN047
to
to
to
A015
00 to 15
SBN240 to SBN255