Tables 46-48 show the input and output channel designations.
Table 46 — I/O Channel Designations Base Module — CV
Table 47 — I/O Channel Designations Base Module — VAV
Table 48 — I/O Channel Designations Expansion Module (Field-Installed) — CV and VAV
                                               LEGEND (Tables 46-48)
NOTE: All even numbered terminals are negative (–) polarity and all
odd numbered terminals are positive (+) polarity.
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
 ASSIGNMENT
T1-2
SPT (CCN) — 10KV Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
STO (CCN) — 10KV Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5KV Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5KV Thermistor
T28-29
Heat 1 Relay — DO (24 vac)
T9-10
T30-29
Heat 2 Relay — DO (24 vac)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
CV Power Exhaust 1/Modulating Power Exhaust — DO (115 vac)
T13-14
IAQ Indoor — AI (4 to 20 mA)
T33-32
CV Power Exhaust 2 — DO (115 vac)
T15-16
IAQ Outdoor — AI (4 to 20 mA)
T34-35
Condenser Fan — DO (115 vac)
T17-25
Y1 or Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
Y2 — DI (24 vac)
T37-38
T19-25
W1 — DI (24 vac)
T39-38
T20-25
W2 — DI (24 vac)
K1
Indoor Fan Relay — DO (LV)
T21-25
G — DI (24 vac)
K2
Compr. 1 — DO (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
 ASSIGNMENT
T1-2
SPT (CCN) — 10KV Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
RAT — 5KV Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5KV Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5KV Thermistor
T28-29
Heat 1 Relay - DO (24 v)
T9-10
T30-29
Heat Interlock Relay — DO (24 v)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
Modulated Power Exhaust — DO (24 vac)
T13-14
IAQ Indoor — AI (4 to 20 mA)
T33-32
T15-16
IAQ Outdoor — AI (4 to 20 mA)
T34-35
Condenser Fan — DO (115 vac)
T17-25
Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
T37-38
Unloader 1 — DO (115 vac)
T19-25
T39-38
Unloader 2 — DO (115 vac)
T20-25
K1
Indoor Fan Relay — DO (LV)
T21-25
K2
Compr. 1 — DO (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
 ASSIGNMENT
T1-2
T23 and TB2-1
Fire — Evacuation — DI (24 vac)
T3-4
T24 and TB2-1
Fire — Smoke Purge — DI (24 vac)
T5-6
T26-27
T7-8
T28-29
T9-10
T30 and TB2-2
Alarm Light Indicator — DO (24 vac)
T11-12
T31
Power Exhaust Fire No. 1 — DO (115 vac)
T13-14
T33
Power Exhaust Fire No. 2 — DO (115 vac)
T15-16
T34
Power Exhaust Fire No. 3 — DO (115 vac)
T17 and TB2-1
Fan Status — DI (24 vac)
T36
Power Exhaust Fire No. 4 — DO (115 vac)
T18 and TB2-1
Filter Status - DI (24 vac)
T37
T19 and TB2-1
Field Applied Status — DI (24 vac)
T39
T20 and TB2-1
Demand Limit — DI (24 vac)
K1
T21 and TB2-1
Fire — Unit Shutdown — DI (24 vac)
K2
T22 and TB2-1
Fire — Pressurization — DI (24 vac)
K3
AI
— Analog Input
OAT — Outdoor-Air Temperature
AO
— Analog Output
OFC — Outdoor Fan Contactor
CCN — Carrier Comfort Network RAT — Return-Air Temperature
CV
— Constant Volume
SAT — Supply-Air Temperature
DI
— Direct Input
SPT — Space Temperature
DO — Direct Output
STO — Space Temperature Offset
HV
— High Voltage
T
— Terminal
IAQ — Indoor Air Quality
TB
— Terminal Block
KV
— Kilo-Ohms
VAV — Variable Air Volume
LV
— Low Voltage