MAXIMUM SHIPPING WEIGHT
Lb
Kg
2535
1150
NOTES:
1. Dimensions in (
) are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 7
8
0
9
(2134) for coil removal. This dimen-
sion can be reduced to 4
8
0
9
(1219) if conditions
permit coil removal from the top.
b. 4
8
0
9
(1219) to combustible surfaces, all four sides
(includes between units).
c. Left side: 4
8
0
9
(1219) for proper condenser coil
airflow.
d. Front: 4
8
0
9
(1219) for control box access.
e. Right side: 4
8
0
9
(1219) for proper operation of
damper and power exhaust (if so equipped).
f. Top: 6
8
0
9
(1829) to assure proper condenser fan
operation.
g. Bottom: 14
9
(356) to combustible surfaces (when
not using curb).
h. Control box side: 3
8
0
9
(914) to ungrounded sur-
faces (non-combustible).
i. Control box side: 3
8
6
9
(1067) to block or concrete
walls, or other grounded surfaces.
j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser
coil and the damper/power exhaust as stated in Note
No. 5, a removable fence or barricade requires no
clearance.
7. Dimensions are from outside of corner post. Allow
0
8
-
5
16
9
(8) on each side for top cover drip edge.
CORNER WEIGHT*
A
B
C
D
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
523
237
541
245
574
260
596
270
*Weights are for unit only and do not include options or crating.
Fig. 5 — Base Unit Dimensions, 48HJ025
6