Goodman Mfg ANSI Z21.47CSA-2.3 用户手册

下载
页码 32
24
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD HORIZONTAL
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
---
---
---
0.00
6827
2.67
6394
2.28
5982
1.94
0.4
---
---
---
---
7079
3.20
6623
2.76
6161
2.34
5706
1.98
5271
1.66
0.6
---
---
6903
3.32
6405
2.83
5923
2.41
5434
2.02
4949
1.68
---
---
0.8
6717
3.42
6198
2.92
5668
2.45
5152
2.05
---
---
---
---
---
---
1.0
5975
2.99
5418
2.51
---
---
---
---
---
---
---
---
---
---
1.2
5147
2.55
---
---
---
---
---
---
---
---
---
---
---
---
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
9359
4.92
8991
3.79
8621
3.54
8188
3.27
7826
3.04
0.4
---
---
9018
3.18
8632
4.39
8251
3.39
7867
3.15
7363
2.85
6992
2.63
0.6
---
---
8279
2.96
7879
3.86
7484
2.99
7085
2.75
---
---
---
---
0.8
7957
4.82
7513
2.73
7097
3.35
---
---
---
---
---
---
---
---
1.0
7179
4.23
6716
2.49
---
---
---
---
---
---
---
---
---
---
1.2
6368
3.66
---
---
---
---
---
---
---
---
---
---
---
---
CPG180 STANDARD  BELT DRIVE 
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6
CPG240 STANDARD  BELT DRIVE 
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6