Generac Power Systems H-100 用户手册

下载
页码 52
  
29
Move the cursor to the “Time Start” time of day min-
utes field on the second line.
Press the “ENTER” button to enter edit mode.
Use the up and down arrow key until the desired 
minute of the hour is displayed.
Press the “ENTER” button to exit edit mode.
Move the cursor to the 
on the bottom line.
Press the “ENTER” button to move to the second 
page.
Move the cursor to the “QuietTest Selected” field on 
the first line.
Press the “ENTER” button to enter edit mode.
Use the up and down arrow key until a “Y” appears.
Press the “ENTER” button to exit edit mode.
NOTE:
Verify that “Xfer On Exercise” field is an “N”. 
Otherwise, QuietTest® will be overridden with 
normal exercise.
General Information
H-100 Control Panel Technical Manual