Assa 32 用户手册

下载
页码 25
Rev. A.5, 8/03 
Page- ii 
PROBLEM
-- Apparent electronic noise interference with the access control system. 
Electric locks, being inductive devices, return voltage spikes on their power wires and also emit microwave 
radiation when switched.  This can interfere with access control electronics causing malfunctions.  Access control 
contractors often employ installation techniques designed to isolate the access control electronics from the electric 
lock.  These include separate circuits for the lock, shielded wiring and other techniques.  These techniques will vary 
with the sensitivity of the access control system electronics and should, of course, be followed.  Note that 
Magnalocks include internal electronics which suppress both inductive kickback and radiation.  They have been 
extensively tested and accepted by numerous access control manufacturers and have been used in thousands of 
installations without incident.  An apparent noise problem is therefore usually not caused by the Magnalock.  The 
access control equipment may be itself faulty or have been installed improperly.  One problem can arise with the 
Magnalock.  If the Senstat version is being used, the strike plate (which passes current) must be isolated from a 
metal door and frame.  Securitron supplies insulating hardware to accomplish this but the hardware might not have 
been used or the strike may be scraping against the header for instance.  Check for full isolation between the strike 
and the door frame (when the door is secure) with an Ohmmeter.  The presence of lock voltage potential in the 
door frame can interfere with the ground reference of access control system data communication and therefore 
cause a problem. 
 
IF YOUR PROBLEM PERSISTS 
CALL SECURITRON TOLL FREE 
1-800-MAG-LOCK 
 
APPENDIX B 
CALCULATING WIRE GAUGE SIZING 
The general practice of wire sizing in a DC circuit is to avoid causing voltage drops in connecting wires which 
reduce the voltage available to operate the device.  As Magnalocks are very low power devices, they can be 
operated long distances from their power source.  For any job that includes long wire runs, the installer must 
be able to calculate the correct gauge of wire to avoid excessive voltage drops.
 
This is done by adding the resistance of the Magnalock to the resistance in the power wires and then dividing the 
wire resistance by the total resistance.  This yields the fraction of voltage drop in the wires.  For example, a single 
model 62 Magnalock has a resistance of 192 ohms when being operated on 24 volts.  If the wires completing the 
circuit between the Magnalock and its power source have a resistance of 10 ohms, the total resistance is 202 
Ohms.  Dividing 10 Ohms (the wire resistance) by 202 (the total resistance) yields roughly 1/20 or 5%.  If the input 
voltage is 24 volts, 5% of this voltage will be dropped in the wires (1.2 volts) leaving 22.8 volts to operate the 
Magnalock.  This will cause a small reduction in holding force but in general, will be acceptable. 
To calculate the wire resistance, you need to know the distance from the power supply to the Magnalock and the 
gauge (thickness) of the wire.  The following chart shows wire resistance per 1000 ft (305 meters): 
Wire Gauge 
Resistance/1,000 ft 
Wire Gauge 
Resistance/1,000 ft 
8 Gauge 
.6 Ohms 
16 Gauge 
4.1 Ohms 
10 Gauge 
1.0 Ohms 
18 Gauge 
6.4 Ohms 
12 Gauge 
1.6 Ohms 
20 Gauge 
10.1 Ohms 
14 Gauge 
2.5 Ohms 
22 Gauge 
16.0 Ohms 
 
Model 32 resistances are 160 Ohms for the 24 VDC version and 40 Ohms for the 12 VDC version. 
Model 34 resistances are 136 Ohms for 24 VDC operation and 34 Ohms for 12 VDC operation. 
Model 62 resistances are 192 Ohms for 24 VDC operation and 48 Ohms for 12 VDC operation. 
Model 82 resistances are 136 Ohms for 24 VDC operation and 34 Ohms for 12 VDC operation. 
Let's look at some other sample calculations.  Suppose a single 62 Magnalock operating on 24 volts is 1200 ft from 
its power supply and we're using 20 gauge wire.  First, the total length of the power wires is 2400 ft.  Remember 
that you combine the wire lengths from the power supply to the lock and back to the power supply to get 
the total circuit wire length.
  The wire resistance than becomes 2.4 X 10.1 Ohms which is 24.2 Ohms.  Adding 
this to the Model 62 Magnalock resistance of 192 Ohms (at 24 volts) yields a total resistance of 216.2 Ohms.  24.2 
divided by 216.2 yields the percent drop in the wires which is over 11% which we would consider excessive.  The 
problem can be dealt with in 2 ways.  You can utilize 16 gauge wire which would reduce the drop to a more 
acceptable 5% range or you can provide extra voltage at the power supply.  For instance, Securitron 24 V power 
supplies are adjustable from 24 to 28 volts.  You can therefore easily set the power supply to output 11% 
overvoltage which will then deliver 24 volts at the lock.  The Magnalock will accept up to 30% overvoltage without ill 
effects.