Williams 1773511 用户手册

下载
页码 24
 
ressure at the correct value 
 
Gas Conversions
 
Converting to another gas type must be performed by a qualified service technician.  If the type of the gas supplied to the 
dwelling is not the same type as your furnace (natural or LPG gas), it must be converted. 
 
It will be necessary to do the following: 
1. Change nozzle. 
     a.   Remove the screw indicated 
           to the right. 
 
 
 
 
 
2. Without removing anything else, remove the nozzle from the burner inserting the screwdriver as indicated by the arrow.  
 
Nozzle
 
 
 
 
 
 
 
3. Change the nozzle, attach the screw indicated at point 1 and set the burner pressure as indicated in the table below: 
 
Gas Type 
Nozzle Part Number 
Nozzle Diameter 
 
Natural Gas 
JGLL065 
0.09 in. 
LP Gas 
JGLL067 
0.05 in. 
 
Minimum Inlet Line Gas 
Pressure 
Maximum  
Minimum  
Gas Type 
Manifold Gas Pressure  
Manifold Gas Pressure 
Natural Gas 
7.0-inches w.c. 
3.2-inches w.c. 
1.8-inches w.c. 
LP Gas 
11.0-inches w.c. 
10.6-inches w.c. 
6.5-inches w.c. 
4.  Check the gas pressure and settings. 
Minimum Burner Pressure Setting: 
1.  Set LOW burner capacity by pressing button Z2 
2.  Connect a micro manometer to the test gauge B (Figure 8) 
3.  Rotate the internal screw “D” (Figure 8) and set the pressure at the correct value 
 
Maximum Burner Pressure Setting: 
1.  Set HI burner capacity by pressing button Z2 
2.  Connect a micro manometer to the test gauge B (Figure 8) 
3.  Rotate the external screw “C”  (Figure 8) and set the p