All installations and services must be performed by qualified service personnel. 
 
D.  FAN AND LIMIT POSITION AND LOCATION 
 
?
?
?
?WARNING:  The predetermined fan and limit locations on all of the Thermo Pride oil fired 
furnaces have been tested and approved by Thermo Products, LLC. in conjunction with 
Underwriters Laboratories, Inc. Any attempt to relocate these safety controls or replace these 
safety controls with a control that is not approved, or is incompatible, may result in personal 
injury, substantial property damage or death. 
 
The units listed in the table below must have the fan and limit control installed at the time of unit installation. A 
locating bracket is provided with each of the units below. 
 
      
TABLE 2: Installation location of 
the fan and limit control for each 
furnace
 
Fig. 7: Fan and limit location for lowboys, horizontal units and highboys. 
 
 
FAN & LIMIT LOCATION FOR HORIZONTAL UNITS WITH AIR CONDITIONING COIL: 
The fan & limit control should be mounted between the H-coil cabinet and furnace. For distances from top of plenum 
and furnace, see Fig. 7. IMPORTANT: Do not try to mount fan/limit in H-coil cabinet. 
 
NOTE:
 The OL2, OC2 and OH2 only, come standard with an oil filter packaged with the furnace. This filter has the 
capacity of filtering down to a 10 micron particle. This is to assure the small diameter burner nozzles in the low 
heating capacity furnaces are installed with a fine filter to help prevent nozzle clogging. 
 
 
E.  BURNER INSTALLATION: 
 
NOTICE:
  Remove all cardboard packing from around chamber before installing burner.