Empire Comfort Systems GWT-50-2 用户手册

下载
页码 20
12426-4-0104 
    Page 11
THERMOSTAT LOCATION (SG MODELS)
CAUTION — Do not run wire behind ß anges of Header Plate 
or in any location where it might be damaged.  
Millivolt wall thermostats are specially designed for use on self-
generating systems.  They should never be used on line or low 
voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside 
wall away from the furnace but in the same room.  
Note:   Use 16 gauge wire to prevent excessive loss of milli-
volts.
Proper operation depends on a good pilot ß ame.  The ß ame must 
cover the top of the thermopile.  Cleaning of the pilot oriÞ ce and 
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system.  Millivolt 
readings should be:
• Across the thermopile terminals, 400-450 millivolts with  
thermostat OFF.
• Across the thermopile terminals, 150-250 millivolts with  
thermostat ON.
•  Across the thermostat wires at the valve, less than 30 millivolts 
with  thermostat ON.
• Across the thermostat wires at the thermostat, less than 5 
millivolts with thermostat ON.  (Dirty pilot or low pressure 
will reduce readings.)
Connect thermostat wires to gas valve as shown in Figure 7.
Figure 7