Instruction Manual – Model CF1400 Oil Burner
Figure 1 - Min. Combustion chamber dimensions
1405
A
L
Figure 2 - Air tube mounting dimensions
E
T
D
1404
G
1
Insertion depth
Air tube to inside of chamber
– 0.25" ± 0.125"
Air tube length
Tube diameter
Install the burner with a 2° pitch as shown.
Air tube 
length
 
(Dimension T)
A.T.C. Codes
(A.T.C. = Air Tube Combination)
Tube A
(Dim. D = 5½")
Tube B
(Dim. D = 5¾")
  6.75"
CF   66 KD
CF   66 KE
10.25"
CF 102 KD
CF 102 KE
13.75"
CF 136 KD
CF 136 KE
17.75"
CF 176 KD
CF 176 KE
Table 2 - Air tube capacity vs. firebox pressure
Firebox 
pressure
(In. w.c.)
Tube A
Tube B
10% turndown No reserve air 10% turndown
0.0
  11.0 GPH
  13.6 GPH
  12.2 GPH
0.2
  10.5 GPH
  13.1 GPH
  11.7 GPH
0.4
  10.1 GPH
  12.5 GPH
  11.2 GPH
0.6
   9.6 GPH
  12.0 GPH
  10.8 GPH
0.8
   9.2 GPH
  11.4 GPH
  10.3 GPH
1.0
   8.7 GPH
  10.9 GPH
   9.8 GPH
Note:  10% turndown indicates sufficient reserve air to reduce the CO
2
 in the 
flue to 90% of its value.
Note: The above ratings may vary 5% due to variations in actual job conditions.
❏  
Verify firing rate
• Refer to appliance manufacturer’s instructions (if avail-
able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in 
Figure 1
. If the appliance dimensions are smaller
than recommended, reduce the firing rate accordingly.
❏  
Verify air tube
• The information in this section may be disregarded if the
air tube is supplied by the appliance manufacturer.
• Two tube arrangements are available –
Tube 
A
 — 4.0 to 11.0 GPH per 
Table 2
Tube 
B
 — 7.0 to 13.6 GPH per 
Table 2
• Maximum firing capacity depends on the firebox pressure.
Use 
Table 2
 to verify the correct air tube type for the firing
rate required. Use Tube 
B
 only when Tube 
A
 cannot pro-
vide the firing rate required.
• See 
Figure 2
 to verify the correct air tube length and air
tube combination code.
Firing rate
 
Minimum dimensions
(refractory-lined)
(wet-base boilers)
A
L
A
L
  0 to   5 gph
  7.0"
25.0"
7.0"
25.0"
  5 to 10 gph
  8.0"
35.0"
8.0"
40.0"