Thermo Products CMA2-75N 用户手册

下载
页码 55
All installations and services must be performed by qualified service personnel. 
 
CMA2-75 
 
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE 
COOLING UNIT 
HTG Speed 
Recommended CLG Speed 
24,000 MED-LOW 
MED-LOW 
 
30,000 MED-LOW 
MED-HIGH 
36,000 MED-LOW HIGH 
 
 
Furnace Airflow (CFM) vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2 0.3 0.4 0.5 0.6  0.7 
Low 
817 797 773 730 668 
620 555 
ML 
1019 995 959 918 869 
821 760 
MH 
1257 1210 1174 1125 1076 
1024 959 
High 
1470 1420 1366 1312 1259 
1196 1127 
 
 
 
Temperature Rise vs. External Static Pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2  0.3  0.4 0.5 0.6  0.7 
Low 
81 
83 
85 
90 
90 106  119 
ML 
65 
66 
69 
72 
76 
80 
87 
MH 
52 55  56  59 
61 
64 
69 
High 
45 46  48  50 52 
55 59 
 
 
 
 
 
 
 
 
 
               
Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure          
0.1 0.2 0.3 0.4 0.5  0.6  0.7 
Low 
3.1 3.0 2.9 2.8 2.7  2.6  2.5 
ML 
3.9 3.8 3.6 3.5 3.3  3.2  3.1 
MH 
4.8 4.6 4.4 4.2 4.1  4.0  3.8 
High 
5.7 5.5 5.4 5.2 5.1  5.0  4.8 
 
 
Blower Motor Watts vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2  0.3  0.4 0.5 0.6  0.7 
Low 
312 303  298  291 280 
273 264 
ML 
400 390  381  366 354 
342 330 
MH 
513 490  478  462 447 
432 413 
High 
624 605  591  573 556 
542 522 
 
 
 
 
 
Recommended operation range 
 
 
 
 
 
 