INSTALLATION 
HORIZONTAL TERMINATION (continued) 
 
NOTE: 
‹ 
The horizontal run of vent must be level, or have a 1/4-inch rise for every 1 foot of run 
toward the termination.  Never allow the vent to run downward.  This could cause high 
temperatures and may present the possibility of a fire. 
 
‹ 
A 2" clearance (airspace) MUST be maintained on all vent pipe. 
 
4.  With the pipe attached to the appliance adapter, slide the appliance into its correct location, 
and mark the wall for a 10" x 10" square hole.  The center of the square hole should line up 
with the centerline of the horizontal pipe as shown in Figure 6.  Cut and frame the 10" 
square hole in the exterior wall where the vent will be terminated.  If the wall being 
penetrated is constructed of non-combustible material, e.g., masonry block or concrete, a  9" 
diameter hole is acceptable. 
 
5.  Position the horizontal vent termination in the center of the 10" square hole, and attach to 
the exterior wall with the four wood screws provided.  Before attaching the Vent 
Termination to the exterior wall, run a bead of non-hardening mastic around its outside 
edges, so as to make a seal between it and the wall. (See Figure 7.)  The arrow on the vent 
cap should point up. (See Figure 6.)  NOTE:  Ensure that proper clearances to combustible 
materials are maintained.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 6
 
Wood Screws 
Apply Mastic to 
All Four Sides
 
Vent Cap 
10” 
(254 mm) 
10” 
(254 mm) 
Vent Opening 
Combustible 
Wall 
Vent Opening Noncombustible Wall 
   7 1/2” 
(190mm) 