GENERAL VENTING INFORMATION:
Canadian Installations
The venting system must be installed in accordance with the current CSA B149 installation code and/or 
local codes having jurisdiction.
U.S.A. Installations
The  venting  system  must  be  installed  in  accordance  with  the  current  National  Fuel  Gas  Code,  ANSI 
Z223.1, and/or local codes having jurisdiction.
The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm) 
when using “B-vent” venting.
We  strongly  recommend  installing  an  approved  chimney  liner  in  an  existing  brick  chimney.  This  will 
maximize the potential draft of the chimney and lessen the effects of slow chimney start-up. 
VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:
Note:
  Please  refer  to  the  chimney  manufacturer’s  installation  instructions  prior  to  commencing  the 
installation.
This unit may be vented to an existing masonry chimney, or where no masonry chimney is available, an 
approved “B-vent” chimney, or any other approved constructed chimney/vent system (see Figure 24 & 25).
Figure 24: Unit top venting styles.
�� ������
����
�� ������
��������
����������
�����
����� ���� �����
�� ��� ��� ��� ��
��������
Figure 26: Draft test place.
Figure 25: Unit rear 
venting style.
20
In  either  case,  the  fireplace  may  be  connected  to 
the  chimney/vent  using  a  4”  (10  cm)  single  wall  vent 
connector.
If  4”  (10  cm)  “B-vent”  is  used  a  minimum  of  1”  (25  mm)  must  be 
maintained between the vent connector and any combustibles.
CAUTION:  A  minimum  vent  height  of  12’  (3.6  m)  from  the  floor  is 
required to effectively vent this fireplace.
SPILLAGE TEST:
A spillage test must be performed prior to leaving the installed fireplace 
with the customer. Perform this test in the following manner:
1. Close all windows and doors in the room.
2. Start all exhaust fans in the house and the furnace blower.
3. Light the fireplace and set to maximum flame adjustment.
When an existing masonry chimney 
is  utilized  for  the  venting,  we 
recommend  the  vent  connector  be 
connected  to  an  approved  4”  (10 
cm) diameter flue liner running the 
full height of the chimney. In many 
jurisdictions  this  flue  liner  may  be 
mandatory.
If  4”  (10  cm)  single  wall  vent  is 
used, a minimum of 6” (15 cm) must 
be  maintained  between  the  vent 
connector and any combustibles.