Initial Installation
QUALIFIED INSTALLERS ONLY
S
TRAIGHT
 V
ERTICAL
 I
NSTALLATION
:
Figure 5: Straight vertical installation. 
This  basic  venting  configuration  shown  are  rough 
guidelines  only.  Follow  national  and  local  codes  for 
other installation options.
For the best venting performance, we recommend a 
total vent height in the range of 10 feet (3.0 m) to 30 
feet (9.1 m). The total horizontal length depends on 
the number of elbows used; a 90° elbow accounts for 
5 feet (1.5 m) of the horizontal run. 
The venting should never slope down, a minimum 1⁄4 
inch (0.6 cm) rise is needed for every 2 feet (61 cm) 
of horizontal is recommended.
If practical, it is best to locate the appliance to permit 
the use of shorter horizontals and fewer elbows.
Number of 90° elbows Maximum total horizontal 
length allowed
2
20 feet (6.1 m)
3
13 feet (4.0 m)
4
6 feet (1.8 m)
5
0 feet (0 m)
Note: Using two (2) 45° elbows is equivalent  to using 
one (1) 90° elbow.
The venting rise should be a minimum of 1 foot (0.31 
m) from the top of the unit before any horizontal run 
are used.
Table 1.  90° elbows allowed verses the 
horizontal length.