Combustible Wall Chimney Connector Pass-Throughs
Method A� 12” (304.8 mm) Clearance to Combustible Wall Member: 
Using a minimum thickness 3.5” (89 mm) brick and a 5/8” (15.9 mm) 
minimum wall thickness clay liner, construct a wall pass-through.  
The clay liner must conform to ASTM C315 (Standard Specifica-
tion  for  Clay  Fire  Linings)  or  its  equivalent.  Keep  a  minimum  of 
12” (304.8 mm) of brick masonry between the clay liner and wall 
combustibles.  The clay liner shall run from the brick masonry outer 
surface to the inner surface of the chimney flue liner but not past 
the inner surface.  Firmly grout or cement the clay liner in place to 
the chimney flue liner.  
Method B� 9” (228.6 mm) Clearance to Combustible Wall Member: 
Using a 6” (152.4 mm) inside diameter, listed, factory-built Solid-
Pak chimney section with insulation of 1” (25.4 mm) or more, build 
a wall pass-through with a minimum 9” (228.6 mm) air space be-
tween the outer wall of the chimney length and wall combustibles.  
Use sheet metal supports fastened securely to wall surfaces on all 
sides, to maintain the 9” (228.6 mm) air space.  When fastening 
supports to chimney length, do not penetrate the chimney liner (the 
inside wall of the Solid-Pak chimney).  The inner end of the Solid-
Pak chimney section shall be flush with the inside of the masonry 
chimney flue, and sealed with a non-water soluble refractory ce-
ment.  Use this cement to also seal to the brick masonry penetra-
tion.
Method C� 6” (152.4 mm) Clearance to Combustible Wall Member: 
Starting with a minimum 24 gage (.024” [.61 mm]) 6” (152.4 mm) 
metal chimney connector, and a minimum 24 gage ventilated wall 
thimble which has two air channels of 1” (25.4 mm) each, construct 
a wall pass-through. There shall be a minimum 6” (152.4) mm sep-
aration area containing fiberglass insulation, from the outer surface 
of the wall thimble to wall combustibles.  Support the wall thimble, 
and cover its opening with a 24-gage minimum sheet metal sup-
port. Maintain the 6” (152.4 mm) space.  There should also be a 
support sized to fit and hold the metal chimney connector. See that 
the supports are fastened securely to wall surfaces on all sides.  
Make sure fasteners used to secure the metal chimney connector 
do not penetrate chimney flue liner.  
Method  D�    2”  (50.8  mm)  Clearance  to  Combustible  Wall  Mem-
ber:  Start  with  a  solid-pak  listed  factory  built  chimney  section  at 
least 12” (304 mm) long, with insulation of 1” (25.4 mm) or more, 
and an inside diameter of 8” (2 inches [51 mm] larger than the 6” 
[152.4  mm]  chimney  connector).  Use  this  as  a  pass-through  for 
a  minimum  24-gauge  single  wall  steel  chimney  connector.  Keep 
solid-pak section concentric with and spaced 1” (25.4 mm) off the 
chimney connector by way of sheet metal support plates at both 
ends of chimney section.  Cover opening with and support chimney 
section on both sides with 24 gage minimum sheet metal supports. 
See that the supports are fastened securely to wall surfaces on all 
sides. Make sure fasteners used to secure chimney flue line
.
NOTES:
1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall 
pass-through system and the chimney wall, to but not past the inner flue liner face.
2.  A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or 
ceiling.