Enviro Indoor Gas Fireplace 用户手册

下载
页码 32
19
Initial Installation
QUALIFIED INSTALLERS ONLY
C
ONVERTING
 A D
IRECT
 V
ENT
 F
IREPLACE
 T
O
 A B-V
ENT
 F
IREPLACE
:
Direct Vent
Connector Assembly
Fresh Air
Inlet Covers
1. Remove  the  Direct  Vent 
chimney  connector  assembly 
by taking out the two (2) T-20 
screws at the front of the unit. 
Push  the  assembly  out  from 
under the brackets at the back 
and remove (see Figure 24). 
2. Remove  the  two  (2)  fresh  air 
inlet  covers  from  each  side. 
Cover  locations  shown  in 
Figure 24.
3. Slide  the  B-Vent  chimney 
connector  assembly  into  the 
same  position  the  Direct  Vent 
chimney  connector  assembly 
was  in.  Ensure  the  tabs  are 
under the brackets at the back 
and the holes at the front line 
up. Secure into place with the 
two  (2)  T-20  screws  at  the 
front of the unit.
4. Disconnect  the  two  (2)  blue 
wires  at  the  opening  to  the 
right  of  the  unit  and  connect 
them  to  the  300°F  (149°C) 
manual  reset  spill  switch  at 
the rear of the B-Vent chimney 
connector  with  the  wires 
supplied. Refer to Figure 25.
5. Test  fire  the  appliance  and 
ensure  proper  operation.  A 
venturi  adjustment  could  be 
required to achieve an efficient 
flame.  Improper  operation 
or  adjustment  could  result  in 
Carbon  Monoxide  production 
causing  personal  injury  or 
property damage.
Figure 24: Converting to a BV fireplace.
B-Vent
Connector Assembly
300°F (149°C)
manual reset
spill switch
Figure 25: Converting to a BV fireplace.