Figure 15.  Floor Level Hearth Requirements With 
Dimensions Around Opening.
Figure 14.  Raised Fireplace with Raised Hearth
F
IREPLACE
 S
URROUND
:
NOTE: Any paint that is applied to the mantel or facing above the unit should be “heat resistance” or it 
may discolour.
Initial Installation
QUALIFIED INSTALLERS ONLY
may be added to the edge of the hearth. The trim can be 
combustible as long as the hearth extends at least 16” 
(406 mm) in front of the fireplace and 1” (25 mm) on 
either side of the fireplace opening (see Figure 15).  To 
install the face, it is necessary for the bottom flange of the 
fireplace opening to overlap or be flush with the tile. If the 
total thickness of the protector pad, cement board, and 
finished tile is more than 11⁄2” (38 mm) the fireplace must 
be raised to accommodate additional thickness. 
If the unit is raised 4” (102mm) or less it is mandatory to have a hearth installed with a protector pad 
(sheet metal) placed directly on the floor or hearth framing, with the cement board 
(see specs below) 
on 
top of it. Tile, or another non-combustible material forms the top layer of the hearth. A decorative trim 
CEMENT  BOARD:  The  cement  board  can 
be fastened to the front of the unit with self-
drilling metal screws. It is safe to screw to the 
outer border of the fireplace. Cement board for 
the hearth can be purchased at a local building 
material store. The board must have a k-value 
of 7.69 Btu/(ft² × h × °F) [13 W/m × K] and a 
R-value of 0.13 ft² × h × °F/Btu [0.023 m² × 
K/W] or better. 
TILED  FINISH:  Because  of  the  amount  of 
heat  exuded  by  the  fireplace,  drywall  cannot 
come  directly  up  to  the  fireplace.    Figure 
15  shows  the  minimum  dimensions  for  the 
cement  board.  Tile  or  other  non-combustible 
materials cover the cement board, but do not 
overlap  into  the  fireplace  opening.  The  total 
depth  of  the  cement  board  and  the  finishing 
materials should be a minimum of 1” (25 mm) 
to  maximum  of  13⁄8”  (35  mm).  The  fireplace 
front will be installed over top of the finishing 
material.  
SMOOTH FINISH: The fireplace will have to 
be recessed by 1⁄2” (12 mm) and two (2) layers 
of  cement  board  must  be  used  if  the  area 
around the fireplace will be finished flush with the rest of the wall.
ROCK OR BRICK FINISH: If the face of the fireplace is to be recessed, the face option chosen will 
determine the size and shape of the surrounding material (i.e. brickwork). Since the dimensions provided 
on the face option instruction sheet are only approximations, it is recommended that the steel template 
of the chosen face is used. See P
ARTS
 L
IST
 - O
PTIONS
  for the face template part number.
14