Raypak NH 用户手册

下载
页码 53
CLEARANCES TO PROTECTED SURFACES
Note 1:
Combustible floor shield is required when heater is to
be installed on a combustible surface. (See ordering
info. on pg.5.)
Note 2:
Servicing Clearances: Provide at least 24" (Models
0133-1826), 48" (Models 2100-4001) in front of unit for
removal & servicing of the Controls & Burner Tray.
Provide at least 18" on side opposite water connec-
tions for deliming of Heat Exchanger Tubes.
*Vent includes factory supplied drafthoods and does
not include field supplied vent systems above the
drafthood.  On Models  2100-4001 drafthood is built
into heater.
CLEARANCES
INSTALLATION CLEARANCES
(All Dimensions Are In Inches)
CLEARANCES FROM COMBUSTIBLE
SURFACES
6
Note: The heater shall be installed in a space large in
comparison to the size of the heater.  Large space is
defined as having a volume at least  sixteen  (16) times
the total volume of the heater.