Installation of Vertical Inlet Baffle
The vertical inlet baffle is to be used only in a completely vertical 
vent installation. The vertical inlet baffle can be used when the 
vertical vent rise is between 10 feet and 40 feet. To maintain the 
yellow flame in the main burner, purchase Vertical Inlet baffle, 
DVF-139 from your Empire Comfort Systems, Inc. distributor or 
dealer for Simpson Duravent only.
In a vertical vent rise the rear (yellow) flame on the main burner can 
be reduced due to the drawing action from the flue exhaust pipe and 
the air inlet pipe. A decrease in the height or the appearance of the 
yellow flame may occur when the vertical vent rise is between 10 
feet and 40 feet. To enhance the yellow flame on the main burner, 
the vertical inlet baffle can be attached to the direct vent high wind 
vertical top.
Please  use  the  following  steps  to  install  the  vertical  inlet 
baffle.
1.  Place the vertical inlet baffle over the exterior of the air inlet 
openings on the direct vent high wind vertical top.
2.  There are three sections of air openings on the exterior of the 
air inlet pipe. 
  To achieve the maximum amount of yellow flame the vertical 
inlet baffle will cover-up three sections of air openings. 
  To achieve the minimum amount of yellow flame the vertical 
inlet baffle will cover-up one section of air openings.
3.  Attach vertical inlet baffle to the direct vent high wind vertical 
top with (2) 3/8" hex-head screws provided with vertical inlet 
baffle.
4.  Installation of vertical inlet baffle is completed.
Parts List
Description
Part 
Number
Quantity 
Supplied
Vertical Inlet Baffle
DVF-139
1
3/8" Hex-Head Screw
R-2656
2
Reassembly and Resealing Vent Pipe System
Attach vent pipe to inlet and outlet vent adaptor on fireplace in either 
the vertical or horizontal position, replace horizontal and vertical 
pipe lengths, elbows and horizontal or vertical termination kit.
All vent system components lock into place by sliding the concentric 
pipe section with four (4) equally spaced interior beads onto the 
appliance collar or previously installed component end with four 
(4) equally spaced indented sections. When the internal beads of 
each starting outer pipe line up, rotate pipe section clockwise 90° 
(approximately 3 inches). The vent pipe is now locked together.
Continue replacing components per the vent system configuration. 
Be certain that each succeeding vent component is securely fitted 
and locked into the preceding component in the vent system.
Reassembly and Resealing Gas Accumulation Relief System
Glass Frame Assembly and Combustion Chamber
Whenever the glass frame assembly  is pivoted open by a delayed 
ignition in the main burner, the glass frame assembly gaskets and 
combustion chamber must be examined by a qualified service person 
for damage. All damaged gaskets on the glass frame assembly and 
combustion chamber must be replaced by a qualified service person. 
If damage occurs to the combustion chamber, it must be replaced 
by a qualified service person. Contact Empire Comfort Systems, 
Inc. for replacement parts.
Vertical Through the Roof Applications (Figure 53)
Your Gas Fireplace has been approved for:
a)  Vertical installations up to 40 feet in height.
b)  Two  sets  of  45  degree  elbow  offsets  within  these  vertical 
installations. From 0 to a maximum of 8 ft. a vent pipe can be 
used between elbows.
c)  Wall straps must be used to support offset pipe every 4'. 
This application will require that you first determine the roof pitch 
and use the appropriate venting components.
Figure 53
VERTICAL TERMINATION (continued)