TABLE 6 - SUPPLY AIR BLOWER PERFORMANCE (15 TON)
180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
4500
5250
6000
6750
7200
ESP
BHP
KW
ESP
BHP
KW
ESP
BHP
KW
ESP
BHP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
850
6.0**
0.9
2.4
2.2
0.7
3.0
2.7
0.5
3.2
2.9
-
-
-
-
-
-
870
5.5
1.0
2.5
2.3
0.8
3.1
2.8
0.6
3.5
3.1
0.2
4.1
3.7
-
-
-
915
4.5
1.1
2.6
2.4
0.9
3.4
3.0
0.7
3.7
3.3
0.3
4.4
3.9
0.2
4.5
4.0
965
3.5
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
4.9
4.4
980
3.0
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1010
2.0
1.4
3.1
2.8
1.2
3.8
3.4
1.0
4.2
3.8
0.7
5.0
4.5
0.6
5.4
4.8
1040
1.0
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.2
4.7
0.7
5.7
5.1
208 VOLT AND HIGH SPEED DRIVE ACCESSORY
965
6.0
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
5.0
4.4
980
5.5
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1025
4.5
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.8
5.1
4.6
0.7
5.6
5.0
1065
3.5
1.6
3.4
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
-
-
-
1095
3.0
1.7
3.5
3.1
1.5
4.2
3.8
1.3
4.9
4.4
1.2
5.7
5.1
-
-
-
1130
2.0
1.9
3.7
3.3
1.7
4.5
4.0
1.5
5.1
4.6
-
-
-
-
-
-
1170
1.0
2.1
3.9
3.5
2.0
4.7
4.2
1.8
5.5
4.9
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
6.0**
1.0
2.4
2.2
0.8
3.1
2.8
0.6
3.5
3.1
0.2
4.1
3.7
-
-
-
915
5.0
1.1
2.6
2.4
0.9
3.3
3.0
0.7
3.7
3.3
0.3
4.4
3.9
0.2
4.5
4.0
965
4.0
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
5.0
4.4
980
3.5
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1040
2.0
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.3
4.7
0.7
5.7
5.1
1065
1.0
1.6
3.3
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
-
-
-
230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY
980
6.0
1.3
2.9
2.6
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1040
4.5
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.3
4.7
0.7
5.7
5.1
1065
4.0
1.6
3.4
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
-
-
-
1095
3.5
1.7
3.5
3.1
1.5
4.2
3.8
1.3
4.9
4.4
1.2
5.7
5.1
-
-
-
1130
2.5
1.9
3.7
3.3
1.7
4.5
4.0
1.5
5.1
4.6
-
-
-
-
-
-
1170
1.5
2.1
3.9
3.5
2.0
4.7
4.2
1.8
5.5
4.9
-
-
-
-
-
-
1190
1.0
2.2
4.0
3.6
2.1
4.8
4.3
2.0
5.7
5.1
-
-
-
-
-
-
  NOTES: 1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry indoor coil and no electric heat.
 
  2. Refer to Page 12 for additional static resistances.
  ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted
  from the total static pressure of the blower.
 * 