VII  Control ] 
- 99 -
HWE08040
GB
-7- Defrost Operation Control
(1) Starting the defrost operation
ŒThe defrost cycle starts when the pipe temperature (TH3), in the following table, or below has continuously been detected for 
3 minutes after the integrated compressor operation time of 50 minutes have passed. 
ŒIf 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced defrost operation 
will start by turning on the forced defrost switch (DIP SW2-7).
ŒEven if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation will be 50 minutes
if defrosting took 12 minutes.
ŒIn the multiple-outdoor-unit system, all of the outdoor units that are in operation go into the defrost mode simultaneously. The
unit(s) that is stopped at the time defrost operation starts remains stopped. 
(2) Defrost operation
(3) Stopping the defrost operation
ŒThe defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3) 
has been continuously detected for 4 minutes (when SW3-4 is set to OFF) or 2 minutes (when SW3-4 is set to ON) that ex-
ceeds the values in the table below.
ŒThe defrost cycle will not end for two minutes once started unless one of the following conditions is met : Pipe temperature 
reaches 25°C [77°F] and SW3-4 is set to OFF OR 
 =25+TH7°C [77°F+TH7] and SW3-4 is set to ON.
*1 (5°C [41°F] 
 25°C [77°F]).
ŒIn the multiple-outdoor-unit system, defrosting is stopped on all units at the same time. 
(4)  Problems during defrost operation
ŒIf a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the
integrated compressor operation time will be set to 20 minutes.
(5)  Change in the number of operating indoor units during defrost operation
ŒEven when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and 
an adjustment will be made after the completion of the defrost operation.
ŒDefrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.
Model
TH3
SW3 - 3 OFF
SW3 - 3 ON
72 model
- 10°C [14°F]
- 5°C [23°F]
96 model
- 10°C [14°F]
- 5°C [23°F]
120 model
- 10°C [14°F]
- 5°C [23°F]
Compressor frequency
Model
Compressor frequency
72 model
65 Hz
96 model
65 Hz
120 model
103 Hz
Outdoor unit fan
Stopped
SV1a
ON 
SV5b, SV5c
ON 
21S4a OFF 
21S4b, 21S4c
OFF 
SV9
OFF 
LEV1 0 
pulses
*1
*1. This value may be greater than 0 pulse depending on the 63LS and TH4 status.
LEV2a 1400 
pulses
LEV2b 1400 
pulses
Model
TH3
SW3 - 4 OFF
SW3 - 4 ON
72 model
10°C [50°F]
5°C [41°F]
96 model
10°C [50°F]
5°C [41°F]
120 model
7°C [45°F]
5°C [41°F]