Mitsubishi Electronics PUHY-P312 用户手册

下载
页码 326
- 38 -
[
II  Restrictions ]
GB
HWE08040
(4) Wiring method
1)   Indoor/outdoor transmission line
Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2)   Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3)   M-NET remote controller wiring
M-NET remote controller is connectable anywhere on 
the indoor-outdoor transmission line.
When 2 remote controllers are connected to the sys-
tem
Refer to the section on Switch Setting.
Performing a group operation (including the group 
operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
4)   LOSSNAY connection
Same as [5] 4.
5)   Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
Proce-
dures
Unit or controller
Address setting 
range
Setting method
Notes
Factory
setting
1
Indoor 
unit
Main unit
IC
01 to 50
Assign the smallest ad-
dress to the main unit in 
the group.
To perform a group 
operation of indoor 
units that have differ-
ent functions, desig-
nate the indoor unit in 
the group with the 
greatest number of 
functions as the main 
unit.
00
Sub unit
Assign sequential num-
bers starting with the ad-
dress of the main unit in 
the same group +1. 
(Main unit address +1, 
main unit address +2, 
main unit address +3, 
etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but 
unique address to each 
of these units after as-
signing an address to all 
indoor units.
None of these ad-
dresses may overlap 
any of the indoor unit 
addresses.
00
3
M-NET 
remote
controller
Main 
remote
controller
RC
101 to 150
Add 100 to the main unit 
address in the group
ŒIt is not necessary to 
set the 100s digit.
ŒTo set the address 
to 200, set the rota-
ry switches to 00.
101
Sub
remote
controller
RC
151 to 200
Add 150 to the main unit 
address in the group
4
Outdoor unit
OC
OS1
OS2
51 to 100
Assign sequential ad-
dress to the outdoor 
units in the same refrig-
erant circuit.  The out-
door units are 
automatically designat-
ed as OC, OS1, and 
OS2. (Note)
To set the address to 
100, set the rotary 
switches to 50.
00