5. Remove the screws, retaining ring and rain gasket
from top of heater.
6. Remove  the  screws,  flue  collar  and  gasket  from
the run side of the tee located in the flue box on
top of the heater.
7. Reverse the components and reattach in the new
location.
8. Make sure that the stainless steel cover, now lo-
cated on the run side of the tee, is sealed to avoid
any flue gas spillage.
Venting Installation Tips
Support piping:
horizontal runs - at least every 5 ft
vertical runs - use braces
under or near elbows
Venting Configurations
For heaters connected to gas vents or chimneys, vent
installations  shall  be  in  accordance  with  the  NFGC
(U.S.), or B149 (Canada), or applicable provisions of
local building codes.
Natural Draft Vertical Venting
(Category I)
Installation 
Natural draft venting uses the natural buoyancy of the
heated flue products to create a thermal driving head
that expels the exhaust gases from the flue. The nega-
tive  draft  must  be  within  the  range  of  -.01  to  -.08  in.
WC as measured 12 in. above the appliance flue out-
let to ensure proper operation. Vent material must be
listed by a nationally recognized test agency.
CAUTION: The silicone vent gaskets must be prop-
erly reinstalled to prevent flue gas leakage. Replace
any torn or worn vent gaskets.
WARNING: Examine  the  venting  system  at  least
once  a  year.  Check  all  joints  and  vent  pipe
connections for tightness, corrosion or deterioration.
The maximum and minimum venting length for Cate-
gory I appliances shall be determined per the NFGC
(U.S.) or B149 (Canada).
The diameter of vent flue pipe should be sized accord-
ing  to  the  NFGC  (U.S.)  and  B149  (Canada).  The
minimum flue pipe diameter for conventional negative
draft venting using double-wall Type B vent is: 5 in. for
Model 302B, 6 in. for Models 402B and 502B, and 8 in.
for Models 652B, 752B and 902B.
The  connection  from  the  appliance  vent  to  the  stack
must be as direct as possible and shall be the same di-
ameter  as,  or  larger  than,  the  vent  outlet.  The
horizontal  breaching  of  a  vent  must  have  an  upward
slope of not less than 1/4 inch per linear foot from the
heater to the vent terminal. The horizontal portions of
the  vent  shall  also  be  supported  for  the  design  and
weight  of  the  material  employed  to  maintain  clear-
ances and to prevent physical damage or separation
of joints.
NOTE: A vent adapter (field-supplied) must be used
to connect Type B vent to the unit.
Fig. 24: Natural Draft Vertical Venting
(Category I)