(2) If the self-diagnostics function fails to operate
10-3. Checking the Indoor and Outdoor Units
(1) Checking the indoor unit
(2) Checking the outdoor unit
(3) Checking the serial communications
 Using the TEST/T-RUN terminals
Check the indoor unit.
Is the fuse blown?
Control
No.
Check items (unit operation)
Replace the controller.
Replace the circuit
board or the fuse.
No indicators illuminate and the 
indoor fan does not rotate.
Check the power voltage.
T-RUN
: Test run (compressor and fan motor turn ON).
TEST/MV : Compresses time to 1/60th (accelerates 
operation by 60 times faster than normal).
Fully opens the electric expansion valve.
Press  EMERGENCY OPERATION button 
of main unit controller, or start operation 
using the remote controller.
 If there are no problems with the above, then check the outdoor unit.
1
Press and hold the TEST RUN button 
on the main unit controller until the buzzer 
sounds 1 time. 
2
The rated voltage must be present between inter-unit wirings 1 and 2.
Connect a 5 kohm resistor between inter-unit cables 2 and 3. When the 
voltage at both ends is measured, approximately 12 to 15 V DC must 
be output and the multimeter pointer must bounce once every 8 
seconds.
Or instead of measuring the voltage, you can insert an LED jig and 
check that the LED flickers once every 8 seconds.
Control
No.
Check items (unit operation)
Apply the rated voltage between outdoor 
unit terminals 1 and 2.
 If there are no problems with the above, then check the indoor unit.
Turn the power OFF before performing short circuiting work.
During the self-diagnostics check, the check results are the first indication when the TEST RUN button is pressed until the buzzer 
sounds 1 time, after the power supply is ON. 
So that the check can be made quickly, indicators blink at first communication after power ON.
Before performing the above checks, press the ON/OFF operation button of indoor unit or remote controller to operate the air conditioner, 
and check that AC 220 to 240V is output to terminals 1 and 2. If it is not output, there is a failure related to the indoor unit power.
1
The control panel LED (red) must illuminate.
Short-circuit the outdoor unit COM terminal 
to the T-RUN terminal.
2
The compressor and fan motor must turn ON about 5 seconds later
after the terminals are shorted.
Normal
Blown
TEST/MV  T-RUN terminals
TEST/MV T-RUN
COM
Circuit
board
Probable location of malfunction
Indoor unit circuit board failure
Outdoor unit circuit board failure
Failure (open circuit, contact failure, etc.) 
in the inter-unit wirings
Outdoor unit circuit board failure
Short-circuit terminals 2 and 3 on 
the outdoor unit terminal plate.
Short-circuit terminals 2 and 3 on 
the indoor unit terminal plate.
Initial self-diagnostics
Control 1 
Control 2
.... OFF
.... Blinking
.... Illuminated
Ion
( 3 )
Timer
( 2 )
Operation
( 1 )
Ion
( 3 )
Timer
( 2 )
Operation
( 1 )
Ion
( 3 )
Timer
( 2 )
Operation
( 1 )