Sanyo SAP-KRV94EHDX 用户手册

下载
页码 85
Insulation 
tester
Probe
Clip
Ground wire
Terminal plate
Copper
tube or
metallic part
Clip
Insulation 
tester
Probe
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Copper
tube or
metallic part
Clip
Insulation 
tester
Probe
Clip
Insulation 
tester
Probe
Metallic 
part
From fan motor,
compressor and 
other parts
11.  CHECKING ELECTRICAL COMPONENTS
11-1.  Measurement of Insulation 
Resistance
The insulation is in good condition if the resistance 
exceeds 1M ohm.
11-1-1. Power Supply Cord
Clamp the grounding wire of power cord with the lead 
clip of the insulation resistance tester and measure the 
resistance by placing a probe on either of the two 
power wires. (Fig. 1)
Then also measure the resistance between the 
grounding and other power terminals. (Fig. 1)
11-1-2. Indoor Unit
Clamp an aluminum plate fin or copper tube with the 
lead clip of the insulation resistance tester and 
measure the resistance by placing a probe on each 
terminal screw where power supply lines are 
connected on the terminal plate. (Fig. 2)
11-1-3. Outdoor Unit
Clamp an aluminum plate fin or copper tube with the 
lead clip of the insulation resistance tester and 
measure the resistance by placing a probe on each 
terminal screw on the terminal plate. (Fig. 2)
Note that the ground line terminal should be skipped 
for the check.
11-1-4. Measurement of Insulation 
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part 
from terminal plate, capacitor, etc. Similarly disconnect 
the connector. Then measure the insulation resistance. 
(Figs. 3 and 4)
Refer to Electric Wiring Diagram.
If the probe cannot enter the poles because the hole is 
too narrow then use a probe with a thinner pin.
NOTE