2AC14 Split System Air Conditioner
14
2
AC
14
B
36
P
-
1
A
 Model Number Guide
Refrigerant – 2 = R22
AC = Split Condensing 
Unit
14 - 14 SEER Nominal
 B = Wire Guard 
L = Louvered 
BC = Wire Guard + 76dBA 
LC = Louvered + 76dBA 
Minor Revision Code
Major Revision Code
Voltage 
P - 208-230v/60hz 
Nominal Capacity 
36 - 36,000 Btuh
Model
Voltage/ Hz/
Phase
Voltage 
Range
Min. 
Circuit 
Amp.
Maximum 
Over 
Current 
Device 
 (amps)
Compressor
Fan Motor
Refrig. 
Charge 
(oz.)
:
Weight (lbs.)
Rated 
Load 
(Amps)
Locked 
Rotor 
(Amps)
Full Load 
Amps
Rated 
HP
Nom. 
RPM
Wire Guard/ 
Louvered
2AC14**18P
208-230/60/1
197 - 253
9.7
15
6.9
35
1.1
1/10
1075
106
185
2AC14**24P
208-230/60/1
197 - 253
11.6
20
8.4
39
1.1
1/10
1075
129
201
2AC14**30P
208-230/60/1
197 - 253
15.2
25
11.3
51
1.1
1/5
1075
154
227
2AC14**36P
208-230/60/1
197 - 253
17.2
30
12.9
61
1.1
1/5
1075
165
226
2AC14*42P
208-230/60/1
197 - 253
21.5
35
16.2
82
1.2
1/4
1075
204
262
2AC14*48P
208-230/60/1
197 - 253
22.6
35
17.1
100
1.2
1/4
1075
208
261
2AC14*60P
208-230/60/1
197 - 253
28.8
50
21.4
137
2.0
1/3
1075
264
270
 Electrical and Physical Data
 
:
  Factory charged for 15 feet of line set. Adjust per Installation Instructions
**  = B, L, BC, LC 
*    = B, L 
 Dimensions (in.) and Sound Ratings
Model
Dimensions
B, L 
Sound Rating 
(dBa)
BC, LC 
Sound Rating 
(dBa)
A - width 
(in.)
B - depth 
(in.)
C - height 
(in.)
2AC14**18P
30
30
25.5
80
76
2AC14**24P
30
30
25.5
80
76
2AC14**30P
30
30
33.5
79
76
2AC14**36P
30
30
33.5
80
76
2AC14*42P
30
30
41.5
76
---
2AC14*48P
30
30
41.5
78
---
2AC14*60P
30
30
41.5
80
---
**  = B, L, BC, LC 
*    = B, L