Goodman Mfg SS-CKF50 用户手册

下载
页码 4
SS-CKF50
P
RODUCT
 S
PECIFICATIONS
P
ERFORMANCE
 R
ATINGS
Outdoor Unit
Indoor Unit
Cooling Capacity (BTU/h)
dBs
Total
Sensible
EER¹
kWI²
CKF24-2*
A24-00-2RA
24,000
16,800
9.0
2.66
76
CA*F1824*6*
24,600
17,400
9.0
2.73
76
CKF36-2*
A36-00-2RA
33,000
23,400
9.0
3.67
76
CA*F3030*6*
34,000
24,200
9.0
3.78
76
CKF36-5*
A36-00-2RA
33,000
23,400
9.0
3.67
76
CA*F3030*6*
34,000
24,200
9.0
3.78
76
CKF48-5*
A48-00-2A
44,000
32,400
9.0
4.89
78
CA*F3636*6*
44,000
32,400
9.0
4.89
78
CKF60-5*
A60-00-2R
55,000
37,800
9.0
6.11
78
CA*F3642*6*
55,000
37,800
9.0
6.11
78
CKF70-5*
A60-00-2R
61,000
41,500
9.0
6.78
80
CA*F4860*6*
62,000
42,000
9.0
6.89
80
A90-00-2R
64,000
43,500
9.0
7.11
80
¹ Energy 
Effi ciency Ratio @ 80°F / 67°F / 95°F
²  kWI = Compressor + Indoor Blower + Outdoor Fan Watts
Note:
When mix-matching outdoor and indoor units, the indoor unit check-fl owrator must match the 
outdoor unit size.
S
PECIFICATIONS
C
K   F
0 3 6
2
A
Revision
Unit Type
E = Commercial Air Conditioner
K = Air Conditioner
P = Heat Pump
Category
C  =  Split Systems
Electrical
1 = 208/230 V, 1 Phase, 60 Hz
2 = 220/240 V, 1 Phase, 50 Hz
3 = 208/230 V, 3 Phase, 60 Hz
5 = 380/415 V, 3 Phase, 50 Hz
Nominal BTU/h
018 = 1.5 tons
024 = 2 tons
030 = 2.5 tons
036 = 3 tons
042 = 3.5 tons 
048 = 4 tons
060 = 5 tons
070 = 5 tons