Goodman Mfg CPG SERIES 用户手册

下载
页码 32
8
Important: If using bottom discharge with roof curb, duct-
work should be attached to the curb prior to installing the
unit. Ductwork dimensions are shown in Roof Curb Installa-
tion Instructions.
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower
than supply air end.
To assist in determining rigging requirements, unit weights
are shown as follows:
CG
B
D
A
C
RETURN
SUPPLY
EVAPORATOR COIL
COMPRESSOR 1
COMPRESSOR 2
Y
X
CORNER & CENTER OF GRAVITY LOCATIONS
090/102
120
150
Corner Weight - A
195
230
335
Corner Weight - B
270
330
390
Corner Weight - C
240
280
295
Corner Weight - D
330
405
345
Unit Shipping Weight
1055
1275
1390
Unit Operating Weight
1030
1235
1365
X (Inches)
55
55
47
Y (Inches)
36
36
33.5
DATA
CPG Weights (lbs)
T
O
 
PREVENT
 
SEVERE
 
DAMAGE
 
TO
 
THE
 
BOTTOM
 
OF
 
THE
 
UNIT
DO
 
NOT
 
FORK
 
LIFT
 
UNIT
 
AFTER
 
WOOD
 
STRUTS
 
HAVE
 
BEEN
 
REMOVED
.
CAUTION
Bring condenser end of unit into alignment with the curb.  With
condenser end of the unit resting on curb member and using
curb as a fulcrum, lower opposite end of the unit until entire
unit is seated on the curb.  When a rectangular cantilever
curb is used, care should be taken to center the unit.  Check
for proper alignment and orientation of supply and return
openings with duct.
R
IGGING
 R
EMOVAL
T
O
 
PREVENT
 
DAMAGE
 
TO
 
THE
 
UNIT
DO
 
NOT
 
ALLOW
 
CRANE
 
HOOKS
 
AND
 
SPREADER
 
BARS
 
TO
 
REST
 
ON
 
THE
 
ROOF
 
OF
 
THE
 
UNIT
.
CAUTION
Remove spreader bars, lifting cables and other rigging equip-
ment.
ELECTRICAL WIRING
HIGH VOLTAGE !
D
ISCONNECT
 
ALL
 
POWER
 
BEFORE
 
SERVICING
 
OR
 
INSTALLING
 
THIS
 
UNIT
. M
ULTIPLE
 
POWER
 
SOURCES
 
MAY
 
BE
 
PRESENT
. F
AILURE
 
TO
 
DO
 
SO
 
MAY
 
CAUSE
 
PROPERTY
 
DAMAGE
PERSONAL
 
INJURY
 
OR
 
DEATH
.
WARNING
HIGH VOLTAGE !
T
O
 
AVOID
 
PERSONAL
 
INJURY
 
OR
 
DEATH
 
DUE
 
TO
 
ELECTRICAL
 
SHOCK
DO
 
NOT
 
TAMPER
 
WITH
 
FACTORY
 
WIRING
. T
HE
 
INTERNAL
 
POWER
 
AND
 
CONTROL
 
WIRING
 
OF
 
THESE
 
UNITS
 
ARE
 
FACTORY
INSTALLED
 
AND
 
HAVE
 
BEEN
 
THOROUGHLY
 
TEST
 
PRIOR
 
TO
 
SHIPMENT
. C
ONTACT
 
YOUR
 
LOCAL
 
REPRESENTATIVE
 
IF
 
ASSISTANCE
 
IS
 
REQUIRED
.
WARNING
T
O
 
PREVENT
 
DAMAGE
 
TO
 
THE
 
WIRING
PROTECT
 
WIRING
 
FROM
 
SHARP
 
EDGES
. F
OLLOW
 
NATIONAL
 
ELECTRICAL
 
CODE
 
AND
 
ALL
 
LOCAL
 
CODES
 
AND
 
ORDINANCES
. D
O
 
NOT
 
ROUTE
 
WIRES
 
THROUGH
 
REMOVABLE
 
ACCESS
 
PANELS
.
CAUTION