Toshiba CEILING TYPE 用户手册

下载
页码 120
– 47 –
6-2.
Chec
k Code List (Indoor)
(Indoor unit detected)
²
  When this w
ar
ning w
as detected bef
ore g
roup constr
uction/address chec
k finish at po
w
er supply w
as tur
ned on, the mode shifts 
automatically to A
U
TO
 address setup mode
.
(Central contr
ol de
vices detected)
NO
TE:
E
ven f
or the same contents of error such as comm
unication error
, the displa
y of chec
k code ma
y diff
er according to detection de
vice
.
When remote controller or centr
al controller detects an error
, it is not necessar
ily related to oper
ation of the air conditione
r. In this list, the chec
k codes that outdoor unit detects are not descr
ibed.
Explanation of err
or contents
No communication from remote controller and netw
or
k adapter
(Also no comm
unication from centr
al control system)
There is error on ser
ial comm
unication betw
een indoor and outdoor units
Same address as y
ours w
as detected.
MCU comm
unication error betw
een main motor and micro computer
Regular comm
unication betw
een indoor master and f
ollo
wer units is impossib
le
.
Open/shor
t w
as detected on heat e
xchanger (TCJ).
Open/shor
t w
as detected on heat e
xchanger (TC).
Open/shor
t w
as detected on room temp
. sensor (T
A).
EEPR
OM error (Other error ma
y be detected.
 If no error
, automatic address is repeated.
There are m
ultiple master units in a g
roup
.
When e
ven one g
roup connection indoor unit e
xists in individual indoor unit.
Indoor g
roup address is unset.
Capacity of indoor unit is unset.
Duplicated setting of centr
al control system address
Abnor
mal stop b
y outside error (CN80) input
An error of indoor A
C
 fan w
as detected.
 (F
an motor ther
mal rela
y wor
ked.)
Float s
witch wo
rk
ed.
Indoor DC f
an error (Ov
er-current/Loc
k, etc.) w
as detected.
In heating operation, an error w
as detected b
y temp
. do
wn of indoor heat e
xchanger sensor
.
Follo
wer unit in g
roup cannot oper
ate b
y w
ar
ning from [E03/L03/L07/L08] of master unit.
Air conditioner operation
Automatic
Operation
reset
contin
uation
¡
×
¡
×
¡
×
¡
×
¡
×
¡
×
¡
×
¡
×
×× ×× ×× ×× ××
¡
×
×× ×× ×× ××
¡
×
¡
×
Chec
k code indication
TCC-LINK central
C05
C06
C12
P30
Representative def
ective position
Centr
al control system comm
unication (send) error
Centr
al control system communication (receiv
e) error
Gener
al-pur
pose de
vice control interf
ace batched w
ar
ning
Group f
ollo
w
er unit is def
ectiv
e.
Explanation of err
or contents
Signal sending oper
ation of centr
al control system is impossib
le
. There are m
ultiple same centr
al de
vices
. (AI-NET)
Signal receiving oper
ation of centr
al control system is impossib
le
.
An error on de
vice connected to gener
al-pur
pose de
vice control interf
ace of e
xclusiv
e to 
TCC-LINK/AI-NET
Group f
ollo
w
er unit is def
ectiv
e.
 (F
or remote controller
, abo
ve-mentioned [
∗∗∗
] details are displa
yed with unit No
.)
Air conditioner operation
Automatic
Operation
reset
contin
uation
——
——
——
——
Chec
k code indication
 Remote contr
oller
E01
E02
E09
Representative def
ective position
No master remote controller
, Remote controller communication (Receiv
e) error
Remote controller comm
unication (Send) error
Duplicated master remote controller
Explanation of err
or contents
Signal cannot be receiv
ed from indoor unit.
 Master remote controller w
as not set.
 (including 2 remote controllers)
Signal cannot be sent to indoor unit.
In 2-remote controller control, both were set as master
.
(Indoor master unit stops w
ar
ning and f
ollo
w
er unit contin
ues oper
ation.)
Air conditioner operation
Automatic
Operation
reset
contin
uation
——
——
×
Chec
k code indication
TCC-LINK central & Remote contr
oller
E03
E04
E08
E10
E18
F01
F02
F10
F29
L03
L07
L08
L09
L20
L30
P01
P10
P12
P19
P31
Representative def
ective position
Regular comm
unication error betw
een indoor and remote controller
Indoor/Outdoor ser
ial error
Duplicated indoor addresses
²
Comm
unication error betw
een indoor MCU
Regular comm
unication error betw
een indoor master and f
ollo
w
er units
Indoor unit, Heat e
xchanger (TCJ) error
Indoor unit, Heat e
xchanger (TC) error
Indoor unit, Room temp
. sensor (T
A) error
Indoor unit, other indoor P
.C
. board error
Duplicated setting of indoor g
roup master unit
²
There is g
roup cab
le in individual indoor unit.
²
Unset indoor g
roup address
²
Unset indoor capacity
Duplicated centr
al control system address
Outside error input to indoor unit (Inter
loc
k)
Indoor unit, A
C
 fan error
Indoor unit, o
verflo
w detection
Indoor unit, DC f
an error
4-w
ay
 v
al
ve system error
Other indoor unit error
(Remote contr
oller detected)