– 86 –
(Example of 2-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by 
connecting singly the wired remote controller 
without remote controller inter-unit wire.
Group address
  Individual    : 0000
  Header unit   : 0001
 Follower 
unit 
: 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address 
→ 1
Indoor unit address 
→ 1
Group address 
→ 1
1
2
2
1
3
2
2
1
2
2
2
2
Indoor
A B
1 2 3
<Operation procedure>
1    2    3    4    5    6    7    8    9    10    11  
END
1
3, 6, 9  
END
 11
2, 5, 8
4, 7, 10   
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
T
9-3. Address Setup (Manual Setting from Remote Controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push 
SET
 + 
CL
 + 
TEST
 buttons
simultaneously for 4 seconds or more.
2
(Line address)
Using the temperature setup 
 / 
 buttons,
set 12  to the CODE No.
3
Using timer time   /   buttons, set the line address.
4
Push 
SET
 button. (OK when display goes on.)
5
(Indoor unit address)
Using the temperature setup 
 / 
 buttons, set 
13
  to the CODE No.
6
Using timer time   /   buttons, set 1 to the line address.
7
Push 
SET
 button. (OK when display goes on.)
8
(Group address)
Using the temperature setup 
 / 
 buttons, set 
14
  to the CODE No.
9
Using timer time   /   buttons, set 
0000
  to Individual, 
0001
 to Header unit, and 
0002
 to
Folloer unit.
10
Push 
SET
 button. (OK when display goes on.)
11
Push 
TEST
 button.
Setup completes. (The status returns to the usual stop status.)