Toshiba RAV-SM802UT-E 用户手册

下载
页码 196
– 32 –
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
RAV-SM802UT-E, RAV-SM802BT-E, RAV-SM802CT-E / RAV-SM802AT-E
Indoor unit
Outdoor unit
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TCJ 
sensor
Air heat exchanger
Strainer
TC sensor
Refrigerant pipe 
at gas side 
Ø15.9
Packet valve
Refrigerant pipe 
at liquid side 
Ø9.5
Packet valve
Packed valve
Outer dia. ØA
Pd
Packed valve 
Outer dia. ØB
Ps
Max.
30m
Min.
5m
TD 
sensor
TS 
sensor
TO sensor
TE
sensor
Distributor
4-way valve
(STF-0213Z)
2-step 
muffler
Ø25 × 200L
Rotary 
compressor
(DA150A1F-20F)
Accumulator
(1000cc)
Heat exchanger
Ø8 ripple, 2 rows, 
20 steps
FP1.3 flat fin
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
R410A 1.6 kg
Cooling
Heating
Revised : Nov. 2006
Standard
Cooling
Overload
Low load
Standard
Heating
Overload
Low load
Pressure
(MPa)
(kg/cm²G)
Pd
Ps
Pd
Ps
3.28
0.86
33.4
  8.8
3.59
1.00
33.6
10.2
1.85
0.83
18.9
  8.5
2.53
0.62
25.8
  6.3
3.42
1.07
34.9
10.9
1.99
0.23
20.3
  2.3
Pipe surface temperature (°C)
Discharge
(TD)
84
82
42
75
80
89
Suction
(TS)
 11
 17
   8
   3
 20
–19
Indoor heat
exchanger
(TC)
10
16
  6
42
54
34
Outdoor heat
exchanger
(TE)
  45
  51
  23
    2
  17
–18
Compressor
revolutions per
second (rps)
*
  83
  76
  35
  95
  50
120
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
28/–
24/18
15/–
–10/(70%)