York HFC-410A 用户手册

下载
页码 44
JOHNSON CONTROLS
42
FORM 100.50-EG5 (108)
mechanically expanded into the end sheets. Coils 
are confi gured in a V-bank confi guration, with indi-
vidual  fl at coils rotated from the vertical plane for 
protection from hail damage for each condensing 
circuit. Condensing coils shall have a subcooler for 
more effi cient, stable operation.
 3.  Compressors: Units shall use industrial-duty her-
metic scroll compressors, piped and charged with 
oil and R-410A refrigerant. Compressors shall have 
an enlarged, liquid-carrying capacity to withstand 
rugged operating conditions. Compressor frame 
shall be cast iron, with cast-iron fi xed and orbiting 
scrolls. Each compressor shall feature a line break, 
designed to protect the compressor from over-tem-
perature and over-current conditions. Compressors 
shall be vibration-isolated from the unit, and installed 
in an easily accessible area of the unit. All compres-
sor-to-pipe connections shall be brazed to minimize 
potential for leaks. Each compressor shall include 
an oil sight glass.
 4.  Low Ambient: Compressors shall operate down to 
0°F Control [optional] by monitoring the refrigeration 
system discharge pressure and adjusting condenser 
airfl ow to maintain the proper head pressure to 
protect compressor operation.
 5.  In-Line Refrigerant Driers: Refrigerant piping in-
cludes thermal-expansion valves with replaceable 
thermostatic elements, high- and low-pressure 
switches, anti-recycling timing device to prevent 
compressor restart for five minutes after shut-
down.
  6.  Freezestat: Freezestats shall be provided to prevent 
coil freeze-up and reduce the risk of liquid fl oodback 
to the compressor.
 7.  Condenser Wire Grill [optional]: The condenser 
section shall be enclosed by a wire grill condenser 
enclosure on the three exposed sides. Plastic fi nish 
shall match the color and salt-spray specifi cations 
of the unit exterior.
 8.  Hot-Gas Bypass [optional on constant-volume 
units]: Hot-gas-bypass piping shall be provided to 
enable compressor unloading to as low as 5% to 
better match cooling demand at low loads, prevent 
excessive cycling of the compressor, and reduce 
the risk of coil freeze-up.
  9.  Compressor-sound treatment [optional]: Compres-
sor sound blankets shall be provided to attenuate 
radiated sound from the compressors.
 10. Service Valves [optional]: Liquid, suction and dis-
charge service valves shall be included to provide 
a means of isolating the refrigerant charge in the 
system so that the refrigeration system may be 
serviced without removing the charge of the unit.
Controls (Simplicity Elite)
 1.  Enclosure: Unit shall be shipped complete with 
factory-confi gured, installed, wired and tested roof-
top unit controller housed in a rain-and-dust-tight 
enclosure with hinged, latched, and gasket sealed 
door.
  2.  Basic Controls: Control shall include automatic start, 
stop, operating, and protection sequences across 
the range of scheduled conditions and transients. 
The rooftop unit controller shall provide automatic 
control of compressor start/stop, energy-saver-
delay and anti-recycle timers, condenser fans, and 
unit alarms. Automatic reset to normal operation 
after power failure. Software stored in nonvolatile 
memory, with programmed setpoints retained in 
lithium battery backed real time clock (RTC) memory 
for minimum 5 years.
  3.  Diagnostics: Upon demand, the controller shall run 
through a self-diagnostic check to verify proper 
operation and sequence loading. The rooftop unit 
controller shall continually monitor all input and out-
put points on the controller and to maintain proper 
operation. The unit shall continue to operate in a 
trouble mode or shut down as necessary to prevent 
an unsafe condition for the building occupants, or to 
prevent damage to the equipment. In the event of 
a unit shutdown or alarm, the operating conditions, 
date and time shall be stored in the shutdown history 
to facilitate service and troubleshooting.
 4.  Controls and BAS Communications
    (RS-485) Modbus: The unit shall include Modbus 
communications directly from the unit controller. 
Equipment that is not native to the unit.
  
fi eld installed Modlinc Gateway device is required 
by the manufacturer to communicate to BACnet 
(MSTP), A control points list shall be provided by 
the manufacturer to facilitate communications 
programming with the building automation system. 
Programming, establishing communications and 
commissioning shall be the responsibility of the in-
stalling controls contractor. Start-up assistance and 
support may be purchased from the manufacturer.
    Analog inputs: 0-10VDC inputs shall be provided 
for remote reset of supply air temperature, and duct 
static pressure
 
  Binary outputs: Dry (or “wet”) contacts shall be pro-
vided for alarm outputs for supply fan fault, cooling/ 
heating fault, or general/sensor faults. Contacts 
shall also be provided for occupied/unoccupied, 
shutdown, smoke purge, exhaust or pressurization 
operations; call for cooling or heating.
Guide Specifi cations 
(continued)