York R-410A ZH/ZJ/ZR Series 用户手册

下载
页码 206
528150-YTG-G-1210
14
Johnson Controls Unitary Products
g. Control board shall monitor each refrigerant safety switch 
independently.
h. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a 
power loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of 
aluminized steel and shall be designed with induced draft com-
bustion with post purge logic, energy saving direct spark igni-
tion, and redundant main gas valve. The heat exchanger shall 
be of the tubular type, constructed of T1-40 aluminized steel for 
corrosion resistance and allowing minimum mixed air entering 
temperature of 40 ºF. Burners shall be of the in-shot type, con-
structed of aluminum-coated steel. All gas piping shall enter the 
unit cabinet at a single location, through either the side or bot-
tom, without any field modifications. An integrated control board 
shall provide timed control of evaporator fan functioning and 
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage gas units shall have two independent 
stages of capacity (70% or 75% 1st stage, 100% 2nd 
stage) 3 through 5 ton and (60% 1st stage, 100% 2nd 
stage) 6-1/2 through 12-1/2 ton.
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements, 
shall be provided in a range of 3 thru 54KW. The heating sec-
tion shall have a primary limit control(s) (automatic reset) to pre-
vent the heating element system from operating at an 
excessive temperature. The Heating Section assembly shall 
slide out of the unit for easy maintenance and service. Units 
with Electric Heating Sections shall be wired for a single point 
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor 
temperature, exceeding maximum load criteria of ARI Standard 
340/360. The compressor, with standard controls, shall be 
capable of operation down to 0 ºF outdoor temperature. Unit 
shall be provided with fan time delay to prevent cold air delivery 
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall 
enter unit cabinet at a single factory provided location and be 
capable of side or bottom entry to minimize roof penetrations 
and avoid unit field modifications. Separate side and bottom 
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years, 
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be 
made available by either/or): 
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER 
– Outdoor and return air dampers that are interlocked and 
positioned by a fully-modulating, spring-return damper 
actuator. The maximum leakage rate for the outdoor air 
intake dampers shall not exceed 2% when dampers are 
fully closed and operating against a pressure differential 
of 0.5 IWG. A unit-mounted potentiometer shall be 
provided to adjust the outdoor and return air damper 
assembly to take in outdoor air to meet the minimum 
ventilation requirement of the conditioned space during 
normal operation. During economizer operation, a mixed-
air temperature control shall modulate the outdoor and 
return air damper assembly to prevent the supply air 
temperature from dropping below 55 ºF. Changeover from 
compressor to economizer operation shall be provided by 
an integral electronic enthalpy control that feeds input into 
the basic module. The outdoor intake opening shall be 
covered with a rain hood that matches the exterior of the 
unit. Water eliminator/filters shall be provided. 
Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss. 
Available with barometric relief or power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and 
return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The 
maximum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in the 
design CFM of outdoor air to meet the ventilation 
requirements of the conditioned space during normal 
operation. Whenever the indoor fan motor is energized, 
the dampers open up to one of two pre-selected positions 
– regardless of the outdoor air enthalpy. Dampers return 
to the fully closed position when the indoor fan motor is 
de-energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For 
applications with high restrictions, units are available with 
optional indoor blower motors that provide higher static 
output and/or higher airflow.
• VARIABLE AIR VOLUME (VAV) - The VAV option using 
a variable frequency drive (VFD) shall be available on
6-1/2 through 12-1/2 ton models for applications requiring 
a constant supply-duct static pressure. Units equipped for 
VAV shall be controlled by a duct pressure transducer 
with a 0 - 5" WC pressure range. The pressure transducer 
shall provide a 0 - 5 VDC output signal to a VAV control 
board which, in turn shall provide a 2 - 10 VDC speed 
reference signal to the VFD. The VAV control board shall 
operate using factory-installed Supply Air, Return Air and 
Outside Air Temperature Sensors with a nominal 
resistance of 10,000 Ohms. Units equipped with VFD's 
shall have factory-installed manual bypass as an option.