FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM
CONTACTOR
FIELD-SUPPLIED
DISCONNECT
SINGLE
PHASE
POWER
SUPPLY
PHASE
POWER
SUPPLY
GROUND
LUG
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
DATA TABLES TO SIZE
THE DISCONNECT
CONTACTOR
GROUND
LUG
FIELD-SUPPLIED
DISCONNECT
THREE
PHASE
POWER
SUPPLY
PHASE
POWER
SUPPLY
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
DATA TABLES TO SIZE
THE DISCONNECT
TABLE 12: ELECTRICAL DATA
MODEL
DNA
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
030
208/230-1-60
187
253
14.7
73
1.1
2.2
21.7
30
30
0.96
40
036
208/230-1-60
187
253
17.3
94
1.1
3.5
26.2
35
35
0.96
40
036
208/230-3-60
187
253
10.9
78
1.1
3.5
18.2
25
25
0.96
75
036
460-3-60
414
504
5.8
40
0.6
1.8
9.6
15
15
0.96
75
042
208/230-1-60
187
253
15.4
86
1.1
3.5
23.9
30
30
0.96
40
042
208/230-3-60
187
253
11.5
88
1.1
3.5
19
25
25
0.96
75
042
460-3-60
414
504
5.8
42
0.6
1.8
9.7
15
15
0.96
75
048
208/230-1-60
187
253
24.4
140
1.3
7
38.8
50
50
0.96
40
048
208/230-3-60
187
253
14.1
105
1.3
7
25.9
35
35
0.96
75
048
460-3-60
414
504
7.1
55
0.7
3.5
13.1
20
20
0.96
75
060
208/230-1-60
187
253
28.9
175
1.3
7
44.4
60
60
0.96
40
060
208/230-3-60
187
253
15.5
125
1.3
7
29.5
40
40
0.96
75
060
460-3-60
414
504
8.9
66.5
0.7
3.5
15.4
20
20
0.96
75
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.
2. Dual element, time delay type.