York AHE18 THRU 60' 用户手册

下载
页码 14
Johnson Controls Unitary Products
13
680210-YTG-B-0311
AIR FLOW DATA - 60 Hz MODELS - 230 VOLT
Models
Blower 
Motor Speed
CFM
@ External Static Pressure - IWC
0.10
0.20
0.30
0.40
0.50
0.60
0.70
230 Volt
AHE18B3XH21
High #5
1075
1041
1003
970
930
885
842
Med High #4
895
845
808
767
709
647
561
Med #3
663
618
557
490
348
267
192
Med Low #2
629
468
356
197
175
68
23
Low #1
629
468
356
197
175
68
23
AHE24B3XH21
High #5
1156
1120
1093
1056
1014
951
862
Med High #4
1021
987
952
918
873
836
787
Med #3
829
789
754
698
654
585
532
Med Low #2
681
621
575
496
435
336
262
Low #1
598
503
437
340
259
203
74
AHE30B3XH21
High #5
1156
1120
1093
1056
1014
951
862
Med High #4
1021
987
952
918
873
836
787
Med #3
829
789
754
698
654
585
532
Med Low #2
681
621
575
496
435
336
262
Low #1
598
503
437
340
259
203
74
AHE36C3XH21
High #5
1465
1415
1360
1307
1246
1183
1118
Med High #4
1260
1204
1142
1075
1008
946
876
Med #3
1088
1022
939
862
782
721
626
Med Low #2
998
810
717
630
562
493
444
Low #1
903
707
411
323
265
152
NA
AHE42D3XH21
High #5
1632
1589
1542
1494
1446
1391
1335
Med High #4
1430
1390
1346
1294
1238
1168
960
Med #3
1238
1198
1145
1082
993
908
805
Med Low #2
1118
1020
947
851
734
666
563
Low #1
998
772
477
418
349
NA
NA
AHE48D3XH21
High #5
1861
1823
1787
1750
1708
1666
1620
Med High #4
1674
1640
1599
1562
1516
1472
1432
Med #3
1442
1405
1358
1311
1262
1197
1108
Med Low #2
1257
1220
1163
1103
1031
942
864
Low #1
1153
1031
967
867
764
718
633
AHE60D3XH21
High #5
2091
2053
2016
1975
1937
1906
1869
Med High #4
1903
1868
1832
1791
1748
1703
1660
Med #3
1634
1598
1562
1516
1468
1422
1350
Med Low #2
1447
1404
1361
1318
1257
1164
1092
Low #1
1268
1203
1148
1073
978
907
839
1. Dry coil conditions only, tested without filters.
Air handler units are CSA listed to UL 1995/CSA C22.2 236-05 up to 0.30" w.c. external static pressure, including air filter, wet coil, and largest kW size heater, unless 
otherwise noted.
Operation not recommended in shaded areas.