Operation: Set Up System Configuration
8
NetworkAIR IR Operation, Maintenance, and Troubleshooting
System Delays
Path: Main > Setup > System # > System Config > System Delays
The System delays protect the Modules in the System from excessive wear and damage, and keep the 
modes from working against each other.
Comp Min ON. 
The Comp Min ON setting does not apply to Systems without compressors. For 
Systems with compressors (direct expansion), the delay begins when the compressor engages, and 
then prevents the compressor from disengaging until the delay has expired. It protects the 
compressors from rapidly cycling between on and off and pushing all of their lubricating oil out into 
the refrigerant line.
Comp Min OFF. 
The Comp Min OFF setting does not apply to Systems without compressors. For 
Systems with compressors (direct expansion), the delay begins when the compressor disengages, and 
then prevents the compressor from engaging until the delay has expired. It protects the compressors 
from rapidly cycling between on and off and pushing all of their lubricating oil out into the refrigerant 
line. 
Cndsr Vlv Dly. 
The Cndsr Vlv Dly setting does not apply to Systems without compressors. For 
Systems with compressors (direct expansion), the "condenser fluid valve close delay" begins when 
the compressors disengage, and then keeps coolant flowing through the heat exchanger until the 
delay expires. Once the delay expires, the condenser fluid valve closes.
Intrstg Dly. 
The Intrstg Dly setting does not apply to Systems without compressors. For Systems 
with compressors (direct expansion), the interstage delay begins when the first compressor (stage 1) 
in a Module engages. It prevents a second compressor (stage 2) in a System from engaging until the 
delay has expired.
Start-up Dly. 
The Start-up Dly applies to all System configurations. The delay begins when the 
System is started and initialized. The System cannot begin operation until this delay has expired. Use 
the start-up delay to restart equipment sequentially in your room after a power loss.
Mode Dly. 
The Mode Dly setting applies to all System configurations. The delay begins when the 
blowers start. It allows the sensors to obtain an accurate reading of the room conditions, and the 
System to check for major alarms before engaging environmental control functions.
Communication Loss Shutdown Delay. 
The Comm Loss Shutdown Dly applies to Multi-
Module Systems. The delay begins when an Expansion Module loses communication with the Main 
Module of a System. If communication is not restored before the delay expires, the Expansion 
Module shuts down. Set the delay for up to twenty-four hours, or select Disabled to cause the 
Expansion Modules to remain operating if communication with the Main Module is lost. 
Reducing the Comp Min ON delay can shorten the lives of your compressors by 
causing excessive wear and damage.
Reducing the Comp Min OFF delay can shorten the lives of your compressors by 
causing excessive wear and damage.