Raypak 302BD-902BD 产品宣传页

下载
页码 2
Catalog No.:  2000.303A 
Effective:  11-15-07 
Replaces:  8-15-07
 
Hi Delta FlexGas – Type H 
Models 302BD-902BD
  
Model            
 
 
 
 
RATES OF FLOW AND PRESSURE DROPS 
 
10°F 
T 20°F 
T 30°F 
Min. Flow
Max. Flow
Model GPM 
P (ft)  GPM  P (ft)  GPM  P (ft)  GPM  P (ft) T GPM P (ft) T
302BD 51  3.2  25  <1.0 N/A N/A 20  <1
25
90
9.8
6
402BD 
68 5.4 34 1.5 22  <1 20 <1 34 90 10.0 7 
502BD 
85 9.2 42 2.3 28 1.1 21 <1 40 90 10.5 9 
652BD 
N/A N/A 55 4.0 36 1.8 28 1.1 40 90 10.7 
12
752BD 
N/A N/A 64 5.5 42 2.5 32 1.6 40 90 11.0 
14
902BD 
N/A N/A 76 8.5 51 3.8 38 2.2 40 90 11.8 
17
Basis is 20 GPM or 40°F 
∆T for minimum flow, 90 GPM for maximum flow. 
NOTE: Pump location 
varies based on model 
and application 
SPECIFICATIONS 
 
 
 
 
Approx.
MBTUH
A
B
G
K T  W  Amp. Shipping
Model Input Output Width
 
Nat 
Pro  NPT    
  Draw* Wt. 
(Lbs)
302BD
300
252
36
41
1-1/4
3/4
2 5 
6 18  6
405
402BD
399 335  43  41 
1-1/4
3/4 
2 6 
18-1/2
470 
502BD
500 420  50 35-1/2 1-1/4
3/4 
2 6 
6 22  6 
570 
652BD
650 546 60-1/2 30-1/2 1-1/4
3/4 
2 8 
27-1/4
615 
752BD
750 630 67-1/2 27-1/2 1-1/4 1-1/4
2 8 
30-3/4
700 
902BD
900 756  78 34-1/2 1-1/4 1-1/4
2 8 
6 36  7 
765 
* Without pump 
NOTES: 
1. Dimensions are in inches 
2.  Rates shown are for natural or propane gas, and 
elevations up to 5,000 feet. For installation above 
5,000 feet, please contact manufacturer. 
3. Required natural gas supply pressure is 7 - 10.5” WC. 
Required propane gas supply pressure is 11 - 13” WC.
Raypak, Inc.  
ƒ  2151 Eastman Avenue, Oxnard, CA  93030  ƒ  (805) 278-5300  ƒ  Fax (800) 872-9725  ƒ  www.raypak.com