97% Thermal Efficiency at Full Rate; Up to 99% at Part Load
100% Factory Fire Tested
Maximum Outlet Water Temperature: 160°F
Minimum Acceptable Inlet Water Temperature: 50°F
Full Safety Diagnostics with History
Footprint: Less Than 10.8 ft
2
Limited Twenty-Five-Year Thermal Shock Warranty
Limited Ten-Year Primary Heat Exchanger Warranty
Limited Five-Year Secondary Heat Exchanger Warranty
Full Electronic Modulation, Constant Ratio 4:1 Turndown
Digital Controller with LCD Display
Status Display Lights
Heat Exchanger
Bronze Headers
ASME HLW Stamped; 160 PSIG
Bronze Headers
ASME HLW Stamped; 160 PSIG
MAWP
National Board Listed
Cupro Nickel Fin Tubing
ASME Powder-Coated Tube Sheet
Silicone High Temp O-Rings
ASME Pressure Relief Valve
Cupro Nickel Fin Tubing
ASME Powder-Coated Tube Sheet
Silicone High Temp O-Rings
ASME Pressure Relief Valve
125 PSIG – Standard (Loose)
150 PSI Air Vent, Auto
T&P Gauge (Loose)
Stainless Steel Secondary Heat
T&P Gauge (Loose)
Stainless Steel Secondary Heat
Exchanger
Stainless Steel Evaporator Plate
Boiler Pump: Bronze, HP,
Boiler Pump: Bronze, HP,
120V, 1
∅, 60Hz
Control
120V, 60Hz, 1Ø, Power Supply
120/24V 60Hz Transformer
Ignition Module
120V, 60Hz, 1Ø, Power Supply
120/24V 60Hz Transformer
Ignition Module
3-Try – Standard
Single-Try – Option C-6
Single-Try – Option C-6
Hot Surface Ignition (HSI)
Remote Flame Sensor
High Limit Control, Auto Reset
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Combustion Air Proving Switch
Freeze Protection
Pump Switch
Pump Time Delay
Blocked Condensate Switch
Remote Flame Sensor
High Limit Control, Auto Reset
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Combustion Air Proving Switch
Freeze Protection
Pump Switch
Pump Time Delay
Blocked Condensate Switch
Control (cont.)
Diagnostics Panel with LCD Display,
Diagnostics Panel with LCD Display,
2 lines, 20 characters
Digital Temperature Control
Water Temperature Sensors (3)
Cold Water Protection
Water Temperature Sensors (3)
Cold Water Protection
Burner
Ultra-Low NOx: Less than 20 PPM
Ultra-Low NOx: Less than 20 PPM
(Natural Gas Only)
Gas Train
Fuel
Fuel
Natural Gas
Propane
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
Electronic Firing Mode (WHP)
Dual-Seat Combination Valve
Electronic Firing Mode (WHP)
Construction
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Water, Gas, Vent,
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Water, Gas, Vent,
Electrical, Comb. Air, Cond. Drain)
Combustion Air Filter
Design Certified ANSI Z21.10.3/CSA 4.3
Design Certified ANSI Z21.10.3/CSA 4.3
Venting
Vent Termination
Vent Termination
Outdoor or Indoor, Vertical –
Option D-11
Indoor, Horizontal – Option D-15
Extractor - Optional
By others
Not required
Not required
Multi-Boiler Digital Temp Controllers
B-36 TempTracker Mod+,
2-4 Water Heaters
B-37 TempTracker Mod+,
5-10 Water Heaters
B-38 TempTracker Mod+,
11-16 Water Heaters
Options
F-10 Low Water Cut-Off, Remote
Probe
I-5
High Limit, Manual Reset,
Adj., 100-200
Adj., 100-200
°F
S-1
Low Gas Pressure Switch,
Manual Reset
Manual Reset
S-2
High Gas Pressure Switch,
Manual Reset
Manual Reset
Z-12 Condensate Neutralizer Kit
Regulatory Agency Requirements
XTherm
™
- Type WHP
Water Heaters
Models 1005-2005