Raypak 300-850 产品宣传页

下载
页码 2
Catalog No.:  2000.17 
Effective:  6-22-09 
Replaces:  New
 
XFyre – Type H 
Models 300-850 
Model 
 
 
 
 
 
 
 
 
Dimensions (in.) 
MBTUH 
Model 
(H7-) 
Input Output 
Length 
Mounting
NPT 
NPT 
Flue Ø 
C/A Ø
Ship 
Weight 
(Lbs.) 
Foot- 
print 
(Ft
2
Amps*
300  300 282 28-1/4 27-9/16 3/4 
 
1-1/2  4 
410  6.6  3 
500 500 470 37-1/4 36-1/4  1 1-1/2  4 
505  7.9  4 
850 850 799 54-1/4 
53-9/16 
1-1/4
580  9.5  5 
 
       Ratings shown are for elevations up to 2,000 feet. For installations at elevations  
       above 2,000 feet, please consult the factory for additional instructions. 
* Current draw is for heater only.
 
(Supply breaker must have delayed trip.)
 
 
RATES OF FLOW AND PRESSURE DROPS 
20ºF ∆T 30ºF 
∆T 40ºF 
∆T 
Min Flow 
Max Flow 
Model 
(H7-) 
GPM 
∆P 
GPM 
∆P 
GPM 
∆P GPM
∆P 
∆T GPM ∆P 
∆T 
300  28 17 19  8  14  5 14 5 40 36 27 17 
500  47 16 31  7  24  4 24 4 40 56 24 18 
850  80  40 53  17  40  10 40 10 40  80  40 20 
              * Closed systems only 
 
 
CLEARANCES
 
Certified
Minimum 
Recomm.
Service 
Front 24” 
24” 
Rear 24” 
24” 
Right 1” 
1” 
Left 1” 
1” 
Top 12”  24” 
Floor 0” 
-- 
Vent 1” 
--