Burnham 1100-H4 用户手册

下载
页码 96
H.
  Operating Instructions.
1.  Follow Operating Instructions to place boiler in 
operation.  See Figure 36.
2.  Electronic Ignition Modules with LED indicators.  
Table 10 cross-references the ignition module 
terminal designations to the ignition terminal 
Figure 7:  lED locations
Ignition Module
Terminal Designation
Wiring Ladder Diagram 
Terminal Number
MV
1
MV/PV
2
PV
3
GND
4
24V (GND)
5
24V
6
SPARK
9
TABlE 10:  IGNITION MODUlE TERMINAl
 
  CROSS-REFERENCE
Yellow LED 
Flash Code
a
Indicates
Recommended Service Action
Heartbeat
Normal Flame Signal
N/A
2
                     Weak Flame Signal - 
System will operate reliably but flame signal is 
less than desired.
Note:  This indication may flash temporarily 
during or shortly after lightoff on some appli-
cations.
Perform routine maintenance to 
assure optimum flame signal.
1
Marginal Flame Signal (less than 1.1 µA) -
System may not operate reliably over time.  
Service call recommended.
Note:  This indication may flash temporarily 
during or shortly after lightoff on some appli-
cations.
Check gas supply, pilot burner, flame 
sense wiring, contamination of flame 
rod, burner ground connection.
OFF
No Flame or Flame Signal -
below minimum threshold for system
        operation.
N/A
a
Flash Code Descriptions
-   Heartbeat:  Constant ½ second bright, ½ second dim cycles.
-   The flash code number signifies that the LED flashes X times at 2Hz, remains off for two 
seconds, and then repeats sequence.
numbers in the wiring ladder diagrams.  The yellow 
LED indicates the status of the flame, see Table 11.  
The green LED indicates the status of the system, 
see Table 12.  See Figure 37 for LED locations.  See 
Figure 38 for Troubleshooting Guide.
TABlE 11:  yEllOW  lED  FlAME CODES