XI Service and Maintenance
The following routine maintenance should be performed on an annual basis:
1) Turn off electrical power and gas supply to the boiler
2) Inspect the flue passages for signs of blockage. If there is any carbon in the combustion chamber or the flue passages,
clean the heat exchanger before proceeding further. See the cleaning procedure below.
3) Remove any debris found in the combustion chamber, being careful not to disturb combustion chamber insulation.
4) Remove all burners, noting the location of the pilot main burner. If burners show signs of deterioration, they should be
replaced (some discoloration around the burner ports is normal). Clean the burners by first brushing the ports with a soft
bristle brush and then vacuuming out any debris through the venturi opening.
5) Inspect the pilot assembly:
Standing Pilots - Check the thermocouple for deterioration (some discoloration of the thermocouple is normal). If any
deterioration is present, replace the thermocouple. Inspect the pilot assembly for deposits and deterioration. Clean or
replace the pilot assembly as necessary.
Intermittent Pilots - Clean any deposits found on the electrode and grounding strap. The ideal gap between the
electrode and the ground strap is 1/8”. Inspect the porcelain for cracks or other deterioration. Replace pilot assembly
if deterioration is found.
6) Inspect the combustion chamber insulation for deterioration.
7) (Intermittent Pilot Boilers) - Inspect the ignition cable insulation for cracks or other deterioration. If deterioration is found,
replace cable.
8) Reinstall burners, being careful to put the pilot main burner in its original location.
9) Inspect all boiler wiring for loose connections or deterioration.
10) Inspect the vent system:
Make sure that the vent system is free of obstructions.
Make sure that all vent system supports are intact.
Inspect joints for signs of condensate or flue gas leakage.
Inspect venting components for corrosion or other deterioration. Replace any defective vent components.
11) Inspect the boiler and hydronic system for leaks.
12) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other gas piping
disturbed during the inspection process for leaks.
CAUTION
LABEL  ALL  WIRES  PRIOR  TO  DISCONNECTION  WHEN  SERVICING  CONTROLS.   WIRING  ERRORS  CAN  CAUSE
IMPROPER  AND  DANGEROUS  OPERATION.   VERIFY  PROPER  OPERATION  AFTER  SERVICING.
CAUTION
WATER  LEAKS  CAN  CAUSE  SEVERE  CORROSION  DAMAGE  TO  THE  BOILER  OR  OTHER  SYSTEM  COMPO-
NENTS.   REPAIR   ANY  LEAKS  FOUND  IMMEDIATELY
.