Crown Boiler 24-07 用户手册

下载
页码 90
25
8.  Combination Label and Crown Logo Plate were 
attached to jacket front panel at time of manufacture.  
If loose or peeling, apply pressure to reset adhesive.
9.  On steam boilers, attach lowest permissible water  
level plate (from steam trim carton) to the front  
panel using sheet metal screws.
10. Tighten all sheet metal screws to complete jacket  
 assembly.
11. RTC Bracket (if used)- install bracket in top right 
corner of front panel with four (4) #8 x 3/4” self 
tapping screws.
F.
  BURNER MOUNTING PLATE - Refer to Figures 16 
and 23.
1.  Using silastic sealant, secure the 3/16” diameter 
rope gasket to the groove along the mounting plate 
opening in the front section.
2.  Install 5/16” x 1” lg. cap screw in lower tapping on 
front section to carry weight of burner mounting 
plate.
3.  Engage bottom slot on burner mounting plate with 
matching bolt in bottom tapping of front section.  
Align mounting holes and fasten the mounting plate 
to the boiler sections with seven (7) remaining 5/16” 
cap screws and washers.  Fully tighten all bolts.
G. 
MOUNT   BURNER   ADAPTER   PLATE   TO  
BURNER   MOUNTING   PLATE.   
Refer to Figures 16 and 23.
1.  In all cases the burner adapter plate carton for the 
specified burner will be provided by Crown.
2.  Open Adaptor Plate carton and remove contents.  
CAUTION
Failure to properly fill all gaps between the
insulation and burner blast tube may result
in damage to the burner
Apply four (4) small dabs of silastic on rear surface 
of adapter plate to temporarily hold gasket in 
place.  Hold adapter plate in position against burner 
mounting plate, align holes and secure with five (5) 
3/8” lock washers and 3/8” x 7/8” lg. cap screws.
3.  Follow burner manufacturer’s instructions using 
gasket material and hardware provided with burner.
4.  USE A HOLE SAW OR KNIFE TO CUT BURNER 
MOUNTING PLATE INSULATION TO MATCH 
HOLE SIZE ON BURNER ADAPTER PLATE.  
After cutting, remove any and all loose pieces of 
insulation which may become lodged or interfere 
with the head of a burner air tube after insertion. 
Confirm that hole in insulation fits snugly around 
burner blast tube. If hole is oversized, use fiberglass 
rope gasket provided with burner to fill in any space 
between insulation and blast tube. If rope gasket 
is not provided with the burner, use 3/8” fiberglass 
rope (provided by others).
5.  For boilers without tankless heaters, proceed 
to Step (Install Steam Trim) or I (Install Water 
Trim).
6.  For boilers with tankless heaters, install the 
tankless heater manifolds according to Figure 37.
Figure 23:  Burner Mounting Plate/Burner Adapter Plate Options