Crown Boiler 24-07 用户手册

下载
页码 90
48
of installation.
5.  ON WATER BOILERS WITH TANKLESS 
HEATERS, set low limit operating control dial at 
190°F and high limit dial 210°F.  Operating control 
must be a minimum of 20° below high limit setting.  
Set differential at 25°.
D.
  ADJUST BURNER according to the Burner Manual.
1.  FLAME FAILURE
  The Series 24 boiler controls operate the burner 
automatically.  If for unknown reasons the burner 
ceases to fire and the reset button on the primary 
control is tripped, the burner has experienced 
ignition failure.  Before pressing the reset button, 
call your serviceman immediately.
WARNING
Do not attempt to start the burner when
excess oil or gas has accumulated in the
combustion chamber, when the unit is full
of vapor, or when the combustion chamber
is very hot.
E.
  RETURN TEMPERATURE CONTROL: Initial 
Set-Up and Operation – The return temperature 
control (RTC) is an important part of the overall boiler 
system.  The primary function of the RTC is to protect 
the boiler from thermal shock and sustained flue gas 
condensation.  The RTC monitors the temperature of 
the water returning into the boiler through a return 
sensor.  The RTC controls the 3-way diverting valve 
mounted on the supply of the boiler to prevent return 
water less than 135º F from entering the boiler.  The 
boiler circulator provides constant and minimum flow 
through the boiler during every heat demand.  Prior 
to the start of any boiler cycle, the diverting valve is 
closed to a full by-pass condition, forcing 100% boiler 
water re-circulation.  The diverting valve opens and 
will continue to open provided the return sensor is 
satisfied.  Conversely, large temperature drops will 
close the diverting valve to a position as to prevent 
low temperature return water.  The RTC along with 
the ancillary components must be properly installed 
as identified in Section III, if there is any possibility 
of system return water temperature less than 135°F.  A 
detailed description of the controller and it’s features 
can be found in the RTC Installation and Maintenance 
Manual.
1.  Initial Start-up - Upon initial start-up, the control 
will be energized, identifying the control name and 
revision on the LED display.  If wired properly, the 
control should be energized at all times.  The RTC 
circuit should be supplied from a different source 
than the burner or boiler circuit.  The RTC control 
should be energized at all times.
2.  Testing – The RTC should be tested on initial start-
up, as well as during any troubleshooting exercise.  
Depressing the test button will activate a test 
sequence and energize the red test light on the front 
of the control.  Each of the controllers outputs and 
relays will be energized and tested.  One may pause 
the test sequence at any time by depressing the test 
button.  See the RTC Installation & Maintenance 
Manual for a detailed description of the sequence 
and the potential error messages.  
a.  Return Sensor - The return sensor must be 
properly connected or an error message will be 
displayed.  Both a short and an open circuit in 
the sensor circuit will cause an error message to 
be displayed and the valve will be moved to a 
partially open position until the error is resolved.
b.  Valve Actuator – During the valve actuator test 
sequence, confirm that the valve travels through 
90 degrees of rotation from a full closed position 
to a full open position.  The pointer on the shaft 
must rotate from “10” to “0” respectively.
3.  Adjust Setpoints – The RTC must have a number of 
setpoints adjusted for proper operation.  Below is 
a summary, however see the RTC Installation and 
Maintenance Manual for more details.  To activate 
the ADJUST menu, simultaneously depress and 
hold the Item,  and  buttons.  ADJUST will 
appear in the upper right hand corner of the LED 
display.
a.  ROOM - Set desired room temperature.  This 
will provide parallel shift to heating curve.  
OUTDR DESIGN OFF
b.  MIX TARGET – This represents a fixed target 
supply temperature when the outdoor reset 
feature in NOT selected. (OUTDR DESIGN = 
OFF)  Set the MIX TARGET temperature to the 
designed boiler supply temperature.  Example:  
If the boiler loop is designed to supply hot water 
to the system at 180ºF, set the MIX TARGET 
to 180ºF.  This is also the same as the operating 
aquastat set point.  The mix target is adjustable 
from 60°F to 200ºF.  The default setting is 180°F.  
NOTE:  This function is only for applications 
where the mix sensor is installed.
c.  MIX DSGN – Mix design temperature represents 
the design heating system supply temperature 
when the outdoor reset feature is selected. 
(OUTDR DESIGN = ON)  This represents the 
design of the system loop.  If unsure of the 
original design temperature, set the MIX DSGN 
to the same temperature as the boiler operating 
aquastat, typically 180ºF.  The MIX DSGN is 
adjustable from 70°F to 210ºF.  The default 
setting is 180°F.
d.  OUTDR DSGN – The outdoor design 
temperature represents the value used in the 
heat loss calculations, when the outdoor reset 
feature is selected. (OUTDR DESIGN = ON)  If 
this value is unknown, use the value found in