 Rear Flued Room Sealed Freestanding Gas Heater
INSTALLATION
OPTIONAL 
WALL THERMOSTAT 
A wall thermostat may be installed if desired. 
Connect the wires as per the wiring diagrams. 
Note that the wires are  connected to the "TH" 
on the gas valve. Use table below to determine 
the maximum wire length:
Note: Preferable if the thermostat is installed 
on an interior wall.
Regency
®
 offers an optional programmable 
thermostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or 
UL approved may be used.
CAUTION
Do not connect the millivolt 
wall thermostat wires 
to the 240V wires.
LOUVRE 
INSTALLATION
Attach the top & bottom louvres to the side stove 
panel using 2 screws per side.
GAS PIPE PRESSURE 
TESTING
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig. (3.45 
kPa).  Disconnect piping from valve at pressures 
over 3.45 kPa.
The manifold pressure is controlled by a regulator 
built into the gas control, and should be checked 
at the pressure test point.
Note:    To properly check gas pressure, both 
inlet and manifold pressures should 
be checked using the valve pressure 
ports on the valve.
1)  Make sure the valve is in the "OFF" posi-
tion.
2)  Loosen the "IN" and/or "OUT" pressure 
tap(s), turning counterclockwise with a 1/8" 
wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" 
pressure tap(s) using a 5/16" ID hose.
4)  Light the pilot and turn the valve to "ON" 
position. Read manometer.
5)  The pressure check should be carried out 
with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.
6)  When fi nished reading manometer, turn 
off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. Note: Screw should be snug, 
but do not over tighten
Valve Description
1) Gas 
on/off 
knob
2)  Manual high/low adjustment
3) Pilot 
Adjustment
4) Thermocouple 
Connection
5) Main 
Operator
6)  Outlet Pressure Tap (Manifold Pressure)
7)  Inlet Pressure Tap (Supply Pressure)
8) Pilot 
Outlet
9)  Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit