Mt. Vernon Pellet Insert (AE)
NOTE:   Check clearances carefully for this type of instal-
lation to ensure adequate room for outside air venting.
Check building codes prior to installation.
•  Installation  MUST  comply  with  local,  regional,  state  and 
national codes and regulations.
•  Consult  local  building,  fi re  offi cials  or  authorities  having 
jurisdiction  about  restrictions,  installation  inspection,  and 
permits.
CAUTION
NOTE:  In Canada only a full reline is allowed per ULC 
S628, ORD ULC C1482-M1990.
B.  Full Reline With Outside Air - Vertical 
Figure 18.1
Outside Air
 Termination 
at
 Chimney Top
(Vertical)
305mm  min. 
below
305mm min. 
above
NOTE;  Use metal plate around 
exhaust vent pipe and seal all 
edges with non-flammable insula-
tion such as mineral wool or 
ceramic.
Do not use high temperature caulk-
ing materials to seal any edge to 
prevent furture serviceability.
NOTE:  In Canada this fi replace insert must be installed 
with a continuous chimney liner of 6 inch (152mm) diam-
eter extending from the fi replace insert to the top of the 
chimney.  The chimney liner must conform to the Class 
3  requirments  of  CAN/ULC-S635,  Standard  for  Lining 
Systems for Extising Masonry or Factory-Built Chimneys 
and Vents, or CAN/ULC-S640, Standard for Lining Sys-
tems for New Masonry Chimneys.