WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED INCLUDING:
1. Turn off AC power before proceeding.
2. Be sure all electrical connections are complete and outlet box is closed before inverter connectors on emergency 
pack are connected.
3. Do not use outdoors.
4. Do not mount near gas or electrical heaters.
5. Do not attempt to service the battery. A sealed, rechargeable, no maintenance battery is used. Do not incinerate or 
mutilate; may burst or release toxic materials. Do not short circuit; may cause burns. Battery acid can cause burns to
skin and eyes. If acid is spilled on skin or eyes, flush with fresh water and contact a physician immediately.
6. Equipment should be mounted in locations and at height where it will not be readily subject to tampering by 
unauthorized personnel.
7. The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition.
8. Do not use the equipment for other than intended use.
9. This unit has more than one power supply connection point. To reduce the risk of electrical shock, disconnect both 
the normal and the emergency power supplies before servicing.
10. Before servicing to prevent electrical shock, disconnect the inverter connectors on the emergency pack (located
inside the ballast housing). Make certain that the switch (if the luminaire is switched) and the unswitched lines to 
the emergency pack are turned off at the fuse box. Servicing should be performed by qualified personnel only.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING LUMINAIRE
This luminaire is intended for installation in accordance with the National Electrical Code and local regulations.
To assure full compliance with local codes and regulations, check with your local electrical inspector before
installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
INSTRUCTION SHEET NO.
IS:EMBW
A0402    
Page 1 of 2
INSTRUCTIONS FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
EMERGENCY LIGHTING DECORATIVE WALL LUMINAIRES
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA  02720
NOTE:  THIS INSTRUCTION SHEET IS TO BE USED IN CONJUNCTION WITH INSTRUCTIONS SUPPLIED FOR THE INSTALLATION OF SPECIFIC 
MODEL BEING INSTALLED. 
SAVE THESE INSTALLATION INSTRUCTIONS
A. WIRING - READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE PROCEEDING
1. Make sure AC power is off at fuse box.
2. Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required for the
emergency pack.
3. The emergency pack must be fed from the same branch circuit as the AC ballast(s).
4. In switched luminaires, emergency pack must be connected ahead of any local switching.
5. Make supply wire connections. Use wire nuts (local hardware item). SEE PAGE 2 FOR WIRING DIAGRAM. Unhook
LOOP from BACKPLATE ASSEMBLY. Push supply wires and connections back into outlet box.
6. After connecting inverter connector, proceed with installing in accordance with instructions provided with luminaire.
WARNING: TO PREVENT HIGH VOLTAGE ON THE RED & YELLOW OUTPUT LEADS PRIOR
TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN INVERTER
CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE
EMERGENCY BALLAST.
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS