Lightolier FBP60 产品宣传页

下载
页码 1
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • D0308
Job Information 
Type:
Job Name: 
Cat. No.: 
Lamp(s): 
Notes:
 
FBP Series Fluorescent Emergency Ballast
  FBP60
Page 1 of 1 
One or Two Lamp Operation 700 Lumens
Lightolier is a Philips group brand
Nickel Cadmium Battery
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
9.4”
(23.9 cm)
2.4”
(6.1 cm)
1.5”
(3.8 cm)
NOTES: 
1.  Maximum non-emergency lumen output can vary 
based on lamp manufacturer, ambient operating 
temperature,and ballast manufacturer.
2.  Maximum emergency lumen output is based on total 
output of one or two lamps, and can vary based on 
lamp manufacturer and ambient operating tempera-
ture.
3.  Maximum emergency lumen output is supported for 
a full 90 minutes of operation.
4.  Consult factory for compatibility, operation and 
performance of lamp types not listed.
Lamp Operation and Performance
   
 
 
 
NON-EMERGENCY 
EMERGENCY OP. 
   LAMP 
WATTAGE 
BASE 
MAX. LUMEN 
MAX. LUMEN 
EMERGENCY 
    TYPE 
 
TYPE 
OUTPUT 
OUTPUT 
LAMP OPERATION
  F20T12 
20 
G13/Med Bi-Pin 
1275 
600 - 700 
One or Two
  F30T12 
30 
G13/Med Bi-Pin 
2350 
600 - 700 
One or Two 
  F40T12 
40 
G13/Med Bi-Pin 
2650 
600 - 700 
One or Two
  F40T12/U 
40 
G13/Med Bi-Pin 
3100 
600 - 700 
One or Two
  F60T12 
50 
FA8/Single-Pin 
3600 
600 - 700 
One
  F72T12 
55 
FA8/Single-Pin 
4500 
600 - 700 
One
  F96T12 
60 
FA8/Single-Pin 
5500 
600 - 700 
One
  F24T12HO 
35 
R17D/Recessed 
1620 
600 - 700 
One
  F36T12HO 
45 
R17D/Recessed 
2800 
600 - 700 
One
  F48T12HO 
60 
R17D/Recessed 
4050 
600 - 700 
One
  F60T12HO 
75 
R17D/Recessed 
5150 
600 - 700 
One
  F72T12HO 
85 
R17D/Recessed 
6350 
600 - 700 
One
  F84T12HO 
100 
R17D/Recessed 
7700 
600 - 700 
One
  F96T12HO 
95 
R17D/Recessed 
8000 
600 - 700 
One
  F48T10 
110 
R17D/Recessed 
6200 
600 - 700 
One
  F17T8 
17 
G13/Med Bi-Pin 
1350 
600 - 700 
One or Two
  F25T8 
25 
G13/Med Bi-Pin 
2150 
600 - 700 
One or Two
  F32T8 
32 
G13/Med Bi-Pin 
2950 
600 - 700 
One or Two
  F32T8/U 
32 
G13/Med Bi-Pin 
2700 
600 - 700 
One or Two
  F40T8 
40 
G13/Med Bi-Pin 
3725 
600 - 700 
One
  F72T8 
35 
FA8/Single-Pin 
3000 
600 - 700 
One
  F96T8 
50 
FA8/Single-Pin 
5950 
600 - 700 
One
  FC6T9 
20 
G10Q/4--Pin 
800 
600 - 700 
One
  FC8T9 
22 
G10Q/4--Pin 
1100 
600 - 700 
One 
 
  FC12T9 
32 
G10Q/4--Pin 
1950 
600 - 700 
One
  FC16T9 
40 
G10Q/4--Pin 
2700 
600 - 700 
One
  F39/36BX 
39 
2G11/4--Pin 
2850 
600 - 700 
One
  F40/30BX 
40 
2G11/4--Pin 
3150 
600 - 700 
One
  F50BX/FT55 
50-55 
2G11/4--Pin 
4300 - 4800 
600 - 700 
One or Two
 Features
 1.  Lamp Operation:  Operates the following lamp types: T8 linear fluorescent, 
T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact fluorescent. 
See Lamp Operation and Performance table for specific lamp performance 
and operation.
 2.  Illumination:  Provides 90 minutes of emergency illumination, and produces 
600-700 lumens initial emergency light output. Can be used with most 17w 
to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps without integral starters 
including U-shaped, HO, VHO, circline, energy saving, and 4 pin compacts. It 
is also compatible with most 1, 2, 3 and 4-lamp electronic, standard, energy 
saving and dimming AC ballasts.
 3. Housing:  Constructed of 20 gauge steel with a white high temperature pow-
der coat paint finish. Slim housing allows for wireway channel mounting on 
most recessed luminaires.
 4.  Electronics:  120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and test 
switch.
 5. Battery:  Maintenance free, sealed nickel cadmium battery has an estimated 
service life of 10 years, and an operating temperature range of 32°F (0°C) to 
131°F (55°C). 
 
 6. Input Power Requirements:  3.5 watts max.
 7.  Warranty:  Electronics: 3 years; Battery: 3 years.
Code Compliance
UL 924 listed. UL damp location listing optional.
UL listed for use within sealed and/or gasketed luminaires.
Complete Fixture consists of ballast unit. select options and accessories below.
Model # 
Max. Lumens 
Lamp Operation
FBP60 
700 
One or Two
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact fac-
tory for other input voltages and frequencies. 
DL = UL Damp Location Listing
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote installa-