MULTIPLE AGM300’s CONNECTED TO A BUILDING MANAGEMENT SYSTEM 
DAISY CHAIN FASHION 
         
 
              RS-485 
        
                                                                         TERMINATOR 
                                                                                 “IN” 
 
 
 
 
TERMINATOR TERMINATOR 
TERMINATOR 
TERMINATOR 
 “OUT” 
“OUT” 
 
“OUT” 
“IN” 
 
 
 
 
 
AGM300 - PC Software 
Programming the AGM300 Using PC Software  
NOTE 1: There are two versions of PC software. Use Version 1.0 with AGM300 units with v1.0 Unit Firmware, 
which were built June 2001 or before (as indicated by a serial number that starts with AF01 or lower). Use 
Version 1.52 or higher with v1.21 Unit Firmware or above, which were built August 2001 or later (as indicated 
by a serial number that starts with AH01 or above). The Firmware version is indicated on the label on the ROM 
module inside the AGM300. 
NOTE 2: The PC software uses COM1 by default.  Therefore, the interface cable should be connected to the 
port configured as COM1 on the PC.  Also, no other software drivers or devices in the PC may control COM1 
when the AGM300 software is in use. 
The connection is made through a standard “straight through” serial port connection.  A three-wire connection is 
used (RXD, TXD, and GND).  No hardware flow control is used.  The AGM300 software automatically 
configures COM1 to match the AGM300 RS-232 communications parameters. 
NOTE 3: Occasionally the laptop connection will not connect properly and only two beeps are heard and the 
program times out. The cure for this is to disconnect the RS-232 cable and cycle power on both the AGM300 
and the laptop. After both the AGM300 and the laptop are up and running connect the RS-232 cable and start 
the software program. 
 
1.  Turn on power to AGM300 and allow it to warm up. 
2.  Connect RS-232 interface cable to PC and RS-232 port on the AGM300. 
3.  Insert software disk into PC. 
4.  Open the AGM300 software using Windows Explorer.  
5.  Upon start up, the program will immediately attempt to download data from the AGM300. Several beeps 
can be heard as the program communicates with the AGM300.  
 NOTE: To move through the screen use the ARROW keys to move up, down, left and right. 
6. Use 
the 
ENTER key to select options and the ESC key to back out of a selection. 
AGM300 
UNIT 1 
NODE 1 
AGM300 
UNIT 2 
NODE 2 
AGM300 
UNIT 3 
NODE 3 
AGM300 
UNIT 4 
NODE 4 
BUILDING 
MANAGEMENT 
SYSTEM