Changing Terminator Switch Settings 
The terminator switch for the RS-485 “TO MONITORS” connector is shipped from the factory in the terminated 
or “IN” position. This is the correct setting if the ADM800 is connected to only one AGM300, or if it is the last 
device on a network chain. If the ADM800 is being installed in the middle of a network, the terminator must be 
moved to the “OUT” position. Refer to Multiple AGM's on Page 12. 
The terminator switch for the RS-485 “TO HOST” connector is shipped from the factory in the terminated or “IN” 
position. This is the correct setting if the ADM800 is the last device on the network chain. If other devices are 
daisy chained through the ADM800, the terminator must be moved to the “OUT” position. Refer to Connecting 
to a Building Management System
 on Page 12. 
Locate each terminator switch and determine its position. If it needs to be moved, carefully slide the switch to 
the proper position. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
RS-485 
TO MONITOR 
Connector 
RS-485 
TO HOST 
Connector 
Terminator for RS-485 
TO HOST 
Connector 
OUT 
 
IN 
Terminator for RS-485 
TO MONITOR 
Connector 
OUT 
 
IN